Configuration and Programming
P/N 06-237058-001
3-45
February 2012
3-3.4
TEST MENU FUNCTIONS
Test Menu
functions enable service personnel to test the SmartOne initiating devices for the ability
to transmit alarm signals. You can also perform alarm-simulation tests for the system’s application
program and can command on control modules connected to the SLC. In addition,
Test Menu
commands are used to initiate a walk test.
Figure 3-37 through Figure 3-41 outline the
Test Menu
functions. Each function is explained in detail
in the remainder of Section 3-3.4.
Figure 3-37. ARIES NET
Link
Test Menu Functions (Fig. 1 of 5)
1
SLC Devices.
Test SLC Initiating Devices.
Purpose
: To manually test the capability of one or
more SmartOne initiating devices (i.e., detectors and monitor modules) to generate and transmit
alarm signals that can be properly interpreted and processed by the ARIES NET
Link
control unit.
Note:
The ARIES NET
Link
control unit automatically runs this test once a day for all the configured
initiating devices on the SLC. The most current test results for all initiating devices are stored
in the SLC Test Results log.
9
Lamp Test. Run a Lamp Test. Purpose:
To test the LEDs on the keypad/display.
12
Battery Test. Run a Battery Test. Purpose
: To measure the standby battery's open-circuit
voltage and the power-supply unit’s output voltage.
CAUTION
Physically disconnect the wiring to all agent-release and pre-action-sprinkler circuits and
activate the global-isolate-outputs routine before testing any SLC initiating devices.
Restore the system to normal operating condition at the conclusion of these tests and any
other functional tests that were performed.
4. TEST
Cont’d
2. Battery Test
3. Lamp Test
1. SLC Devices
Start Device Test
SLC Devices From *__ to ___
(1-255)
ENTER SLC LOOP NUMBER (1-8) _
*=Level-2 (Installer ) Password required
1
12
9
Summary of Contents for ARIES NETLink
Page 2: ......
Page 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 293: ......