Operation
P/N 06-237058-001
4-19
February 2012
4-10.3.6.1
What to Do When Alarm Verification Occurs
Press the <SYSTEM ACKNOWLEDGE> Key to silence the internal buzzer. The display will change
appearance. Acknowledgments of alarm verifications are logged.
Figure 4-29. Alarm Verification Acknowledgment Message
The upper line of the LCD display shows the verification time remaining to receive an alarm
confirmation signal from the smoke detector. The verification time will continually decrease in one-
second intervals. The control unit will return to Normal Mode if the smoke detector does not
reconfirm the alarm condition or if no other alarm-initiating device reports at any time prior to the
expiration of the verification period. A verification off event is stored in the event log if neither an
alarm reconfirmation nor a secondary-alarm message is reported.
4-10.4
Supervisory State
The ARIES NET
Link
control unit enters the Supervisory State when an initiating event occurs such
as a monitor module report of a low-air-pressure condition in a pre-action-sprinkler system. It also
occurs when any SLC-based initiating or control device, or any control unit based output circuit, is
isolated.
The upper line of the LCD display shows the supervisory event by the device address, the state
change, and the device type. The lower line indicates the up-to-40-character message assigned to the
supervisory device using the ARIES NET
Link
remote configuration software.
Figure 4-30. Typical Supervisory Message Display
The following actions also occur when any supervisory condition is reported:
•
The Supervisory LED flashes
•
The internal buzzer pulses
•
The supervisory event is stored in the event log
•
The supervisory message is transmitted to peripheral devices (such as Remote Display Control
Modules and Remote LED Annunciator Modules), if applicable
•
The supervisory message is communicated via the RS232 ports
•
Point- or group-specific and general supervisory outputs will activate, including previously-
silenced outputs.
L1:010 ALARM VERIFY PHOTO 00 SEC
CONTROL ROOM
DISCHARGE-00 CNTDN-00 ABT-00 ALM-00
PREALM-00 AVCNTDN-00 SPV-000 TBL-000
A
l
arm
Verification
I
ndication
(on
Smo
k
e
Detectors
On
ly
)
Device
-
Specific
Custom
M
essa
g
e
SLC
Loop
Number
1
Device
Address
0
1
0
Device
T
y
pe
Reportin
g
A
l
arm
-
Verification
On
Time
Remainin
g
for
A
l
arm
Verification
L1:002 SUPERVISORY ON SPV
COMPUTER DATA AREA
DISCHARGE-00 CNTDN-00 ABT-00 ALM-00
PREALM-00 AVCNTDN-00 SPV-000 TBL-000
Supervisor
y
On
I
ndication
Device
-
Specific
Custom
M
essa
g
e
SLC
Loop
Number
1
Device
Address
002
Device
T
y
pe
Number
of
Supervisor
y E
vents
Summary of Contents for ARIES NETLink
Page 2: ......
Page 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 293: ......