Operation
P/N 06-237058-001
4-3
February 2012
4-4
OPERATOR CONTROL KEYS
Operator Control Keys are provided to allow the operator to perform critical functions with the touch
of one button. Table 4-2 lists the Operator Control Keys and their built-in functions.
Table 4-2. Operator Control Keys and Their Functions
BUTTON
FUNCTION
<PROGRAMMABLE SOFT KEYS> The four (4) <SOFTKEYS> can be programmed using the ARIES NET
Link
menu
system or the remote configuration software (ACT 8000). Each of these 4 keys can
be used to program any of the following functions: 1) Isolation Macros; 2) Ground
Fault Maintenance Mode; 3) Battery Tests; 4) Call for Service; 5) SLC Device Test;
6) Walk Test; 7) SLC Device voltage readings; or 8) SLC Line resistance readings
<SYSTEM ACKNOWLEDGE>
The <SYSTEM ACKNOWLEDGE> Key allows the operator to signal the ARIES
NET
Link
system that a new event currently being displayed is understood. The
control unit's audible notification appliance will silence and all flashing Pre-Alarm,
Alarm, Supervisory, or Trouble LEDs will light steadily when all active events have
been acknowledged.
<SYSTEM RESET>
The <SYSTEM RESET> Key restores the ARIES NET
Link
system to Normal
Operation after all alarm system events have been acknowledged and have ceased
reporting alarm conditions.
<SIGNAL SILENCE>
Pressing the <SIGNAL SILENCE> Key after all current alarm events have been
acknowledged shuts off any active, silenceable outputs, such as notification-
appliance circuits or control modules.
There is a 10-second buffer period during which subsequent presses of the
<SIGNAL SILENCE> Key are intentionally ignored. A subsequent key press will
only be acted upon after at least 10 seconds have elapsed since the previous key
press.
Note:
The <SIGNAL SILENCE> Inhibit feature, which disables use of the
<SIGNAL SILENCE> Key, can be programmed for 1, 3 and 5 minutes.
<DRILL/HOLD FOR LAMP TEST> Pressing the <DRILL/HOLD FOR LAMP TEST> Key one time activates a Fire Drill.
Each NAC and/or control module which has been configured for drill operation will
be activated. Pressing the <SYSTEM RESET> Key will end the Fire Drill and
return the system to Normal Operation.
Pressing and holding the <DRILL/HOLD FOR LAMP TEST> Key tests the LEDs on
the User Interface. All of the LEDs should illuminate while the key is depressed.
Releasing the key will extinguish the LEDs.
<SCROLL UP/SCROLL DOWN>
The <SCROLL> Keys allow the operator to view all currently-active events by time
of occurrence. Also used to navigate through the menu options.
Summary of Contents for ARIES NETLink
Page 2: ......
Page 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 293: ......