Operation
February 2012
4-4
P/N 06-237058-001
4-4.1
User Interface Button Operations
Some of the above operations can also be performed for the LAM, ATM, and SLC based Addressable
Input devices.
The LAM can perfom the following operations:
The ATM can perform the following operations:
BUTTON
FUNCTION
<SYSTEM ACKNOWLEDGE>
The <SYSTEM ACKNOWLEDGE> Key allows the operator to signal the ARIES
NET
Link
system that a new event currently being displayed is understood. The
control unit's audible notification appliance will silence and all flashing Pre-Alarm,
Alarm, Supervisory, or Trouble LEDs will light steadily when all active events have
been acknowledged.
<SIGNAL SILENCE>
Pressing the <SIGNAL SILENCE> Key after all current alarm events have been
acknowledged shuts off any active, silenceable control-unit-based or signaling-
linecircuit-based outputs, such as notification-appliance circuits or control
modules. There is a 10-second buffer period during which subsequent presses of
the <SIGNAL SILENCE> Key are intentionally ignored. A subsequent key press
will only be acted upon after at least 10 seconds have elapsed since the previous
key press. Note: The <SIGNAL SILENCE> Inhibit feature, which disables use of
the <SIGNAL SILENCE> Key, can be programmed for 1, 3 and 5 minutes.
BUTTON
FUNCTION
<SYSTEM ACKNOWLEDGE>
The <SYSTEM ACKNOWLEDGE> Key allows the operator to signal the ARIES
NET
Link
system that a new event currently being displayed is understood. The
control unit's audible notification appliance will silence and all flashing Pre-Alarm,
Alarm, Supervisory, or Trouble LEDs will light steadily when all active events have
been acknowledged.
<SYSTEM RESET>
The <SYSTEM RESET> Key restores the ARIES NET
Link
system to Normal
Operation after all alarm system events have been acknowledged and have ceased
reporting alarm conditions.
<SIGNAL SILENCE>
Pressing the <SIGNAL SILENCE> Key after all current alarm events have been
acknowledged shuts off any active, silenceable control-unit-based or signaling-
linecircuit-based outputs, such as notification-appliance circuits or control
modules. There is a 10-second buffer period during which subsequent presses of
the <SIGNAL SILENCE> Key are intentionally ignored. A subsequent key press
will only be acted upon after at least 10 seconds have elapsed since the previous
key press. Note: The <SIGNAL SILENCE> Inhibit feature, which disables use of
the <SIGNAL SILENCE> Key, can be programmed for 1, 3 and 5 minutes.
<DRILL>
Pressing the <DRILL> switch input one time activates a Fire Drill.
Each NAC and/or control module which has been configured for drill operation will
be activated. Pressing the <SYSTEM RESET> or <SIGNAL SILENCE>Key will
end the Fire Drill and return the system to Normal Operation.
Summary of Contents for ARIES NETLink
Page 2: ......
Page 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 293: ......