BACnet Flow Controller (BFC)
Installation
Sample line string: Krown-X-X//
I/SUPPLY/24/48//RSR/HEPA/FC/ECM/115/CF/R+TMB/BACnet/
BFC
/TC/DSW-115//
ASSP///WPF/PL-AL/F-AL/PL-B12/F-B12
Step 1:
Wire unit according to appropriate wiring diagram. If Power Cord (PC) option is selected, simply insert plug end into
electrical socket.
NOTE:
Polarity is important and must be observed. It is also vital that the 24 VAC common side of the transformer be Earth
grounded.
Step 2:
Hook up applicable BACnet, and/or local Building Automation System (BAS) according to wiring diagram. Multiple
units can be daisy chained together using optional RJ45 cables. If using BAS or Local Set point, reference the airflow
setpoint section on the next page.
Daisy Chained Krown Fan Filter Units
Step 3:
Wire the unit according to the appropriate wiring diagram. If power cord option is selected, simply insert the plug end
into the electric socket.
Sample line string: Krown-X-X//
I/SUPPLY/24/48//RSR/HEPA/FC/ECM/115/CF/R+TMB/BACnet/BFC/TC/DSW-115/
PC-115
/
ASSP///WPF/PL-AL/F-AL/PL-B12/F-B12
Step 4:
If the unit has an RSR filter install the filter now, refer to the filter installation section of this manual for instructions.
Step 5:
Ensure proper Voltage is hooked up to the unit.
For additional information on BACnet, and the BFC controller, refer to the
BACnet Wiring Guidelines
, and
BFC Manual
available on KeystoneCleanAir.com
BACnet MS/TP to
BACnet IP Router
Krown 1
Krown 2
Krown 3
Krown 30
Krown 4
Network
Connection
IP Router
Webserver Interface
FFU 1
CFM - 312
FIlter Hours - 1280
Filter Status - Clean
ANTEROOM
FFU 2
CFM - 310
FIlter Hours - 1125
Filter Status - Clean
FFU 3
CFM - 312
FIlter Hours - 1225
Filter Status - Replace
FFU 4
CFM - 310
FIlter Hours - 1300
Filter Status - Clean
FFU 5
CFM - 312
FIlter Hours - 1430
Filter Status - Clean
FFU 6
CFM - 315
FIlter Hours - 1400
Filter Status - Replace
FFU 7
CFM - 312
FIlter Hours - 1350
Filter Status - Clean