ECMSC
Installation
Sample line string:
Krown-X-X//I/SUPPLY/24/48//RSR/HEPA/FC/ECM/115/CF/R+TMB//
ECMSC
/TC/DSW-115//ASSP///
WPF/PL-AL/F-AL/PL-B12/F-B12
Sample line string:
KrownCS-X-X//I/ECM/ECMSC/
WMSC-30
////
Step 1:
Wire the unit according to appropriate wiring diagram. If Power Cord (PC) option is selected, simply insert plug end
into electrical socket.
Potentiometer (POT)
Measure (+) VDC
Measure (-) VDC
WMSC-30
ECMSC Speed Controller
Step 2:
If ECMSC is to be controlled
using analog voltage signal from
BAS (others) or Price WMSC, please
remove ECMSC from control box.
Connect 0-10VDC & COMMON to
BAS SIGNAL & BAS COMMON on
back of ECMSC (make sure to feed
wires through grommet on control
box). Re-fasten ECMSC to control
box.
Step 3:
If the unit has an RSR filter
install the filter now, refer to the
filter installation section of this
manual for instructions.
Step 4:
Ensure proper Voltage is
hooked up to the unit.
Step 5:
Proceed to the following
page to determine the initial test
point voltage (VDC) based on your
scheduled flow rate.
For more information visit
KeystoneCleanAir.com
v001