39
SUPERtrol-I LE Flow Computer
8.2.11
Pulse out test
Sub-menu Group
Press Enter key to test the pulse output.
To simulate a frequency on the pulse output: Connect a
frequency counter to (+)TB1-13,
(-)TB1-14. Press the key under the desired frequency
setting to move the asterisk (*). The unit should output
the selected frequency.
Press Menu key to return to Pulse out test top-level
menu.
Press Enter to test the relays.
To manually control the relay outputs: Press the key
under the desired relay to toggle the relays On/Off. Use
an ohmmeter to check the relay contacts.
Press Menu key to return to Relay Test top-level menu.
Press Enter to test the control inputs.
To check the control inputs: Use TB1-12 as reference,
input a DC voltage (4-24VDC) signal to TB1-9, TB1-10
and/or TB1-11, The Display will show ON when input is
active, OFF when inactive.
Press Menu key to return to control input test top-level
menu.
Press Enter to access data logger utility.
The displays shows the number of Data Logs.
Press the Down arrow key to advance to PRT (print) or
CLR (clear) to clear datalog contents.
Press PRINT key to output data logger logs to printer.
Press CLEAR key to clear the data logger contents.
Press Menu key to return to Data logger utility top-level
menu.
8.2.12
Relay test
Sub-menu Group
8.2.13
Control inputs test
Sub-menu Group
8.2.14
Data logger utility
Sub-menu Group
Pulse out test
Pulse out test
*0Hz 1Hz 10Hz 20Hz
Pulse out test
Relay Test
Rly1 Rly2 Rly3 Rly4
Off Off Off Off
Relay Test
Control inputs test
TB1-9 TB1-10 TB1-11
Off Off Off
Control inputs test
Data logger utility
Data logger utility
Log 10 958 Max
Data logger utility
Log 00001 PRT CLR
Data logger utility