UL Listing Requirement
All control panel designs restrict the number of NAC devices installed in circuits based on the rated
current threshold. Some control panel designs further restrict the number of NAC devices installed in
circuits based on device synchronization in addition to the rated current threshold. These control
panel designs can reduce the population of NAC devices below the number of devices that would be
considered for the rated current threshold.
NAC outputs of the Sigma A-CP Fire Control Panel are not limited by conditions other than the maximum rated
current threshold. NAC outputs of the Sigma A-CP Fire Control Panel can operate combinations of Kentec
authorized NAC devices as long as the total load of NAC 1 and NAC 2 does not exceed 4 A.
The following series of Gentex NAC devices are compatible for use on the special application outputs of
NAC 1 and NAC 2 when operating each NAC output below 2.5 A:
Name of Series
Environment
Model Series
Description
Mounting Type
WSSPK Series
Outdoor
WSSPK24-15/75
Speaker Strobe
Wall
SSPK24WLP Series
Indoor
SSPK24WLP
Speaker Strobe
Wall
SSPKCLP Series
Indoor
SSPK24CLP
Speaker Strobe
Ceiling
Commander4 Series
Indoor
GCC24
Horn Strobe
Ceiling
Commander4 Series
Indoor
GCS24
Strobe
Ceiling
Commander3 Series
Indoor
GEC3-24
Horn Strobe
Wall
Commander3 Series
Indoor
GES3-24
Strobe
Wall
Commander3 Series
Indoor
GEH24
Horn
Wall
Commander2 Series
Indoor
GEC24
Horn Strobe
Wall
Commander2 Series
Indoor
GES24
Strobe
Wall
Commander2 Series
Indoor
GEH24
Horn
Wall