Code Function
Description
31
Set Z1, Alarm Delayed
These functions are not UL recognized.
Sets an alarm delay from the detector to the zone
based on Alarm Delay codes 0-9. Program these
functions to operate by setting code Ad in Access
Level 2.
These functions are disabled unless set by code Ad in
Access Level 2.
32
Set Z2, Alarm Delayed
33
Set Z3, Alarm Delayed
34
Set Z4, Alarm Delayed
35
Set Z5, Alarm Delayed
36
Set Z6, Alarm Delayed
37
Set Z7, Alarm Delayed
38
Set Z8, Alarm Delayed
41
Set Z1, Alarm Verification
Setting this function enables alarm verification on the
Zone.
“A feature of automatic fire-detection and alarm
systems to reduce unwanted alarms wherein smoke
detectors report alarm conditions for a minimum
period of time, or confirm alarm conditions for a given
period of time after reset, in order to be accepted as a
valid alarm initiation.” – UL 864. 3.8 Alarm Verification
42
Set Z2, Alarm Verification
43
Set Z3, Alarm Verification
44
Set Z4, Alarm Verification
45
Set Z5, Alarm Verification
46
Set Z6, Alarm Verification
47
Set Z7, Alarm Verification
48
Set Z8, Alarm Verification
51
Set Z1, Coincidence
These functions are not supported.
Setting this function enables Zone Coincidence.
52
Set Z2, Coincidence