Code Function
Description
13
Set Amseco Alarm Mode
Sets the fire control panel to operate NAC devices
from Amseco.
14
Set Gentex Alarm Mode
Sets the fire control panel to operate NAC devices
from Gentex.
15
Set System Sensor Alarm Mode
Sets the fire control panel to operate NAC devices
from System Sensor.
16
Set Wheelock Alarm Mode
Sets the fire control panel to operate NAC devices
from Wheelock.
21
Disable Fire Alarm Buzzer
Disables operation of the internal buzzer during a fire
alarm condition.
22
Disable Trbl. Relay
Disables operation of the trouble relay except during
a power failure.
23
Disable Earth Trbl.
Disables operation of the Earth Trbl. so that earth-
ground trouble conditions are not reported.
24
Set Strobe Activation
During Alarm Silence
Sets NAC strobes to activate during an alarm silence.
This function is only available when activating
settings for Amseco, Gentex, System Sensor or
Wheelock using codes 13, 14, 15 or 16.
25
Set Zone 1 Class A Operation
Sets Zone 1 for Class A operation using the terminals
of Z1 and Z1 RET. Zone 1 operates as Class B and the
terminals of Z1 RET are unused when this code
is not set.
26
Disable Fire Relay
Disables activation of the Fire relay.
27
Remove Aux 24 V
On Panel Reset
Sets the AUX 24 V output to switch off for five
seconds during a reset of the fire control panel.
28
Remove Aux 24 V
On Fire Alarm
Sets the AUX 24 V output to switch off during a fire
alarm condition.
www.acornfiresecurity.com
www.acornfiresecurity.com