Code Function
Description
A1
Set Z1, Alarm Must Persist for 30 Seconds
These codes set 30 second alarm duration before
reporting. Alarm must persist for 30 seconds before
conditions are reported.
These codes are used when a device could report a
condition unintentionally.
A2
Set Z2, Alarm Must Persist for 30 Seconds
A3
Set Z3, Alarm Must Persist for 30 Seconds
A4
Set Z4, Alarm Must Persist for 30 Seconds
A5
Set Z6, Alarm Must Persist for 30 Seconds
A6
Set Z7, Alarm Must Persist for 30 Seconds
A7
Set Z8, Alarm Must Persist for 30 Seconds
A8
Set Z9, Alarm Must Persist for 30 Seconds
E1
Set Z1, Fire Relay Deactivated
Deactivates the fire relay of the programmed zone.
These functions ”deactivate” the fire relay from
operating a programmed zone only. These functions
do not “disable” the fire relay from operating. Zones
not programmed through these functions continue to
operate the fire relay under fire conditions.
These functions prevent an activating zone from
activating the fire relay.
E2
Set Z2, Fire Relay Deactivated
E3
Set Z3, Fire Relay Deactivated
E4
Set Z4, Fire Relay Deactivated
E5
Set Z5, Fire Relay Deactivated
E6
Set Z6, Fire Relay Deactivated
E7
Set Z7, Fire Relay Deactivated
E8
Set Z8, Fire Relay Deactivated