Configuration Code Zone Short Circuit Supervision
74
Zone 4
75
Zone 5
76
Zone 6
77
Zone 7
78
Zone 8
Reference Section 4, Programming and Operating for further information regarding this configuration
option. The maximum number of detectors per zone is device and manufacturer dependent.
The figure below illustrates a Detector and Pull Station connection on the zone terminals of the Sigma
A-CP Fire Control Panel:
Figure 3- 6
Detector and Pull Station Connection
Zones of the Sigma A-CP Fire Control Panel are not listed to operate more than one detector in the alarm
condition. Reference Appendix B, Detectors for the maximum number of devices permitted per circuit. The
value provided identifies the maximum number of devices permitted to operate on the zone circuit.
6.8K End Of
Line Resistor
(EOLR)
Detector
+ In
+ Out
- In
- Out
+ In
+ Out
- In
- Out
Zone
+ -
Pull Station