Configuration Codes
Not all configuration codes of the Sigma A-CP Fire Control Panel are authorized for operation under
UL 864.
Reference Appendix G, UL 864 Permitted Configurations for the list of authorized configuration codes of the
Sigma A-CP Fire Control Panel.
The configuration codes described below are disabled unless indicated
The table below describes configuration codes of Access Level 3:
Code Function
Description
00
Set Alarm Delay = 30 Seconds
These functions are not UL recognized.
Sets NAC delay in combination with Zone Alarm
codes 31 to 38. Program this function by setting code
Ad in Access Level 2.
These functions are disabled unless set by code Ad in
Access Level 2.
01
Set Alarm Delay = 1 Minute
02
Set Alarm Delay = 2 Minute
03
Set Alarm Delay = 3 Minute
04
Set Alarm Delay = 4 Minute
05
Set Alarm Delay = 5 Minute
06
Set Alarm Delay = 6 Minute
07
Set Alarm Delay = 7 Minute
08
Set Alarm Delay = 8 Minute
09
Set Alarm Delay = 9 Minute
10
Set Steady Alarm Mode
Sets NAC output to steady On
11
Set March Time Alarm Mode
Sets the frequency of the NACs for the March Time
coding pattern of ½ second on, ½ second off and then
repeat.
12
Set Temporal Alarm Mode
Sets the frequency of the NACs for the Temporal
coding pattern of ½ second on, ½ second off, ½
second on, ½ second off, ½ second on, 1½ second off
and then repeat.
www.acornfiresecurity.com
www.acornfiresecurity.com