4
Turn the Enable Access key to the left to exit Access Level 2.
The Test Mode On LED and the Alarm In Zone LED remain lit and the Mode LED is no longer lit.
Disablements
Disablements prevent false alarms when performing building maintenance or construction. Use this
function to disable sections of the fire control system for testing purposes.
Disabling and Re-enabling Zones
This section describes disabling and re-enabling zones. Disable zones for testing and troubleshooting.
Re-enable zones following the disabling process.
Disabling Zones
To disable zones on the Sigma A-CP Fire Control Panel:
1
Turn the Enable Access key to the right to obtain Access Level 2 of the menu.
2
Press Mode (+10) until “d1” appears in the first field of the LED display.
3
Press Select (+1) to scroll through codes d1-d8 for disabling.
Codes d1-d8 correspond to zones Z1-Z8.
4
Press Enter to disable zone codes in the d1-d8 range.
Zone codes that are programmed for disabling contain a flashing dot in the lower-right-corner of the Mode
LED.
Trouble/ Test /Disablement LEDs of the zone in test light and Disablement LED lights.
5
Turn the Enable Access key to the left to exit Access Level 2.
The Trouble/ Test /Disablement LEDs and the Disablement LED remain lit and the Mode LED is no longer lit.
Re-enabling Zones
To re-enable zones on the Sigma A-CP Fire Control Panel:
1
Turn the Enable Access key to the right to obtain Access Level 2 of the menu.
2
Press Mode (+10) until “d1” appears in the first field of the LED display.
3
Press Select (+1) to scroll to the disabled codes.
4
Press Enter to re-enable zone codes in the d1-d8 range.