Colour code
Meaning
Data point
Green
Flashing
Normal state
Orange/Green
Flashing alternately
Configured display
Status LED Information
Red/Green
Flashing alternately
Failure parameter malfunctioning
Status LED Warning
Red
Flashing
All Failure parameters malfunctioning
Status LED Error
Red
Continuous
At least one driver has not started
properly
The time zone can be set to localise the system. Based on this time zone, summer and winter
time are set automatically.
The display of the time can be amended in the configuration software. A full system restart is
necessary to activate the settings.
Time synchronisation via BACnet can only be used if the BACnet driver is installed and one time
synchronisation master has been identified in the BACnet network. Please consult with your
BACnet network coordinator.
To synchronise time via NTP, an NTP server must be reachable from the IP network. Please con-
sult with your system administrator.
The KHS BACnet gateway has a status LED with three colours to provide fast guidance about
the current operating state. The LED features the colours green, red and orange (mixed colour).
System initialisation is identified by an orange LED.
Following initialisation, the status LED flashes green.
Status table - LED in normal operation
7.10
Status LED