Operating instructions CellaCast PX 8x
7 Electrical connection
The pyrometer is supplied with low voltage 24 DC (18 ��� 32 V DC)�
ATTENTION
The device may only be installed by a skilled, qualified electrician� Do not con-
nect it while the voltage supply source is turned on� Please observe international
safety regulations at all times�
►
Disconnect the pyrometer from any voltage source�
►
Connect the pyrometer according to the following schematic�
2
3
1
4
5
1
4
L+
L-
24 V DC
5
C/Q
2
0/4 - 20 mA
Out 2
3
shielded
Pin 1
BN (brown)
L+ (Power supply24V DC)
Pin 4
BK (black)
Open Collector switching output; I
max
= 150 mA
or IO-Link OUT 1
Pin 5
GY (grey)
Open Collector switching output; I
max
= 150 m OUT2
Pin 2 WH (wheite)
Analogue output; 0/4 ��� 20mA
Pin 3
BU (blue)
L- (GND)
The pyrometer must be protected against electromagnetic fields�
Therefore, use a shielded cable, connecting it via connector casing
of the pyrometer to the housing�
Use a flyback diode when switching inductive loads�