installation manual
23
SW 4 Difinition
SW4
ON
1 2
l
00 means temp.compensation
value is 6
℃
under heat mode
SW4
ON
1 2
l
01 means temp.compensation
value is 2
℃
under heat mode
SW4
ON
1 2
l
10 means temp.compensation
value is 4
℃
under heat mode
SW4
ON
1 2
l
11 means temp.compensation
value is 8
℃
under heat mode
SW 6 Difinition
SW6
ON
1234
l
1 means old display penal
l
0 means new display penal
SW6
ON
1234
l
1means DC fan is chosen
l
0means AC fan is chosen
SW6
ON
1234
l
1means factory test mode
l
0means auto addressing mode
(
default setting
)
SW6
ON
1234
l
reserved
For 200/250/280 models
● For A SYSTEM
SW 2 Difinition
SW 3 Difinition
SW 4 Difinition
SW4
ON
1 2
l
00 means temp.compensation
value is 6
℃
under heat mode
SW4
ON
1 2
l
01 means temp.compensation
value is 2
℃
under heat mode
SW4
ON
1 2
l
10 means temp.compensation
value is 4
℃
under heat mode
SW4
ON
1 2
l
11 means temp.compensation
value is 8
℃
under heat mode
SW 6 Difinition
SW6
ON
1234
l
1 means old display penal
l
0 means new display penal
SW6
ON
1234
l
1means DC fan is chosen
l
0means AC fan is chosen
SW6
ON
1234
l
1means factory test mode
l
0means auto addressing mode
(
default setting
)
SW6
ON
1234
l
reserved
● For B SYSTEM
SW 1 Difinition
SW 2 Difinition
SW3
ON
1 2
l
00 means the time of stopping
TERMAL fan is 4 mintues
SW3
ON
1 2
l
01 means the time of stopping
TERMAL fan is 8 mintues
SW3
ON
1 2
l
10 means the time of stopping
TERMAL fan is 12 mintues
SW3
ON
1 2
l
11 means the time of stopping
TERMAL fan is 16 mintues
SW1
ON
1234
l
1means factory test mode
l
0means auto addressing mode
(
default setting
)
SW1
ON
1234
l
1means DC fan is chosen
l
0means AC fan is chosen
SW1
ON
1234
l
reserved
SW1
ON
1234
l
reserved
SW2
ON
1 2
l
00 means shutting down the
unit to"stop cold air" at 15
℃
SW2
ON
1 2
l
01 means shutting down the
unit to"stop cold air" at 20
℃
SW2
ON
1 2
l
10 means shutting down the
unit to"stop cold air" at 24
℃
SW2
ON
1 2
l
11 means shutting down the
unit to"stop cold air" at 26
℃
ON
SW2
1234
l
00 means shutting down the unit
to “stop cold air” at 15
℃
ON
SW2
1234
l
01 means shutting down the unit
to “stop cold air” at 20
℃
ON
SW2
1234
l
10 means shutting down the unit
to “stop cold air” at 24
℃
ON
SW2
1234
l
11 means shutting down the unit
to “stop cold air” at 26
℃
ON
SW2
1234
l
00 means the time of stopping
TERMAL fan is 4 mintue
ON
SW2
1234
l
01 means the time of stopping
TERMAL fan is 8 mintue
ON
SW2
1234
l
10 means the time of stopping
TERMAL fan is 12 mintue
ON
SW2
1234
l
11 means the time of stopping
TERMAL fan is 16 mintue