16.  TEST OPERATION

 

The test operation must be carried out after the entire installation 
has been completed.

 

 

 

 

Operation lamp 

Timer indicator 

Alarm indicator

 

Please confirm the following points before the test operation:

 

 

●  The indoor unit and outdoor unit are installed properly. 

 

PRE-DEF indicator(cooling and heating type) 
or fan only indicator(cooling only type)

 

●  Tubing and wiring are correctly completed. 

Fig.13-1

 

14.

 

INSTALL ELECTRIC THROTTLE PART

 

Please refer to the following figures to install.

 

●  The refrigerant pipe system is leakage-checked.

 

 

●  The drainage is unimpeded.

 

 

●  The heating insulation works well.

 

 
 
 

 

Connective Pipe 1

 

 
 

 

Connective Pipe 2

 

 
 
 

 

15.

 

INSTALL BRANCH PIPE

 

Hi-pressure pipe

 

 
 
 
 
 
 

 

Fig.14-1

 

 
 

 

Low-pressure pipe

 

 

●  The ground wiring is connected correctly.

 

 

●  The length of the tubing and the added stow capacity of the 

refrigerant have been recorded.

 

 

●  The power voltage fits the rated voltage of the air conditioner.

 

 

●  There is no obstacle at the outlet and inlet of the outdoor and 

indoor and indoor units

 

 

●  The gas-side and liquid-side stop valve are both opened.

 

For 7.1KW~16KW models

 

●  The air conditioner is pre-heated by turning on the power.

 

 
 
 
 

Liquid branch pipe 

Gas branch pipe

 

 
 

 

For 20KW~28KW models

 

 

Electric throttle part

 

 
 

Φ9.5mm

 

 

Φ15.9mm

 

 

 

Hi-pressure pipe

 

 
 
 

 

Fig.15-1

 

 

Low-pressure pipe

 

According to the user’s requirement, install the remote controller 
frame where the remote controller’s signal can reach the indoor 
unit smoothly.

 

 

Test operation

 

Set the air conditioner under the mode of “COOLING” with the 
remote controller, and check the following points per the “Owner’s 
Manual” If there is  any malfunction, please resolve it  through 
chapter “Troubles And Causes ”in the “Owner’s Manual”.

 

●  The indoor unit

 

 
 

 

Liquid branch pipe 

Gas branch pipe

 

 

≤10m

 

Φ9.5mm

 

Φ9.5mm

 

 
 
 
 

 

Φ15.9mm

 

Φ15.9mm

 

 
 
 
 
 

 

Fig.15-2

 

 

Whether the switch on the remote controller works well. 

Whether the buttons on the remote controller works well. 

Whether the air flow louver moves normally.

 

Whether the room temperature is adjusted well.

 

 

The piping diameter please refer to the manual of the outdoor unit you choose.

 

 

 

Branch Part should be installed in horizontal mode or vertical 
mode.

 

 

Whether the indicator lights normally. 

Whether the temporary buttons works well.

 

 
 
 

Install horizontally

 

Install vertically

 

Main pipe is vertical 
to horizontal plane

 

 
 
 
 
 
 
 
 
 

 

Fig.15-3

 

Whether the drainage is normal.

 

Whether there is vibration or abnormal noise during operation.

 

 

Whether the air conditioner heats well in the case of the 
HEATING/COOLING type.

 

 

●  The outdoor unit

 

 

Whether there is vibration or abnormal noise during operation.

 

 

Whether the generated wind, noise, or condensed water by the 
air conditioner have influenced your neighborhood.

 

 

Whether any of the refrigerant is leaked.

 

 

 
 
 
 

 

Fig.15-4

 

CAUTION

 

 

Protection  function  will  delay  the  startup  of  compressor  for  3 
minutes  in  case  the  unit  is  turned  on  immediately  after  power 
on or restarted after shutdown.

 

 

 

  

 

  

 

A

 

B

 

Summary of Contents for KPDHF-71 DN3.0

Page 1: ...0 DN3 0 KPDHF 160 DN3 0 KPDHF 200 DN3 0 KPDHF 250 DN3 0 KPDHF 280 DN3 0 The Digital Scroll and DC AC Inverter share the same indoor units Thank you very much for purchasing our air conditioner Before...

Page 2: ...MD14I 041FW DZ2 16100101A01132...

Page 3: ...nce and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do n...

Page 4: ...ive and negative poles are in right positions when loading batteries 4 INDOOR UNIT INSTALLATION Installing 10 Hanging Screw Bolts 4 Bolts Please refer to the following figure for the distance measurem...

Page 5: ...eel refer to Fig 4 4 Overhanging the indoor unit Fig 4 4 Fig 4 7 Overhang the indoor unit onto the hanging screw bolts with block Position the indoor unit in a flat level by using the level indicator...

Page 6: ...ONNECTION SAFETY DRAIN CONNECTING PIPE AIR OUTLET 255 33 65 722 65 Fig 4 9 14 16KW 135 930 88 Unit mm PLASTIC COVER 68 24 46 ELECTRICAL CONTROL BOX 4 12 25OBLONGSUSPENTIONBOLTHOLES AIR INTAKE CONNECTI...

Page 7: ...w as Fig 4 11 SafetyDrainTray Fig 4 12 2 Remove the all 11 screw from fixed Safety Drain Tray and then take off the tray as figure showed in Fig 5 11 3 Take off the tray along the direction of the arr...

Page 8: ...all 4 bolts from reinforced panel and take off the panel 3 Refer to Fig 4 13 remove all 4 bolts from fan assembly see Fig 4 14 according to which orders to take off the fanassembly 4 Refer to Fig 4 1...

Page 9: ...11 screw from fixed Safety Drain Tray and then take off the tray as figure showed inFig 4 16 3 Take off the tray along the direction of the arrow show in Fig 4 16 4 Clean the tray and evaporator 5 Re...

Page 10: ...m fan assembly see Fig 4 18 according to which orders to take off the fan assembly 3 Refer to Fig 4 18 horizontal pushing the fan assembly until it cannot not move any further and then lift up slightl...

Page 11: ...nnection 9 52 3 8 Refrigerant pipe flared connection 16 5 8 Air intake duct flange 1270 Connecting point of drain pipe 43 125 100 Air intake 936 200 Fig 4 19 The method of installation adopt following...

Page 12: ...onfirm that there is enough room for installation and mainte nance Maintenance roomage Maintenance roomage motor assembly bottom cover plate screw Confirm the minimum drain tilt is 1 100 or more check...

Page 13: ...ut dust filter dust adherent on the air heat exchanger may cause failure and water leak Key points of duct connection Canvas tie in Canvas tie in Fig 7 1 Other assemblies should be prepared on spot ex...

Page 14: ...12 9KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 7 Fig 7 5 11 2KW model fan curve the static pressure refer to Table 12 2 Middle fan speed Fig 7 6 Hig...

Page 15: ...installation manual 13 Middle fan speed 14KW model fan curve the static pressure refer to Table 12 2 High fan speed Low fan speed Fig 7 9 Fig 7 10 Middle fan speed Fig 7 11 Fig 7 12...

Page 16: ...installation manual 14 Low fan speed Middle fan speed Fig 7 13 16KW model fan curve the static pressure refer to Table 12 2 Low fan speed Fig 7 15 High fan speed Fig 7 16 Fig 7 14...

Page 17: ...20KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 19 Middle fan speed Fig 7 17 25KW 28KW model fan curve the static pressure refer to Table 12 2 High fan...

Page 18: ...1 Hang the outside frame on the main body with face down 4 places at 4 corners Hang the belt on the hook of the main body Low fan speed Fig 7 22 The signal wire of the remote control receiver must be...

Page 19: ...urities may enter the pipe system and may cause malfunction later So please expel the air out of the pipe with refrigerant before connection Expel the air refer to the Expel The Air after connectingth...

Page 20: ...pipe cutter Insert a flare nut into a pipe and flare the pipe lean crude burr 9 2 Check The Leakage Fig 9 1 Fasten the nut Put the connecting tubing at the proper position wrench the nuts with hands...

Page 21: ...l should be more than 50mm and the drain pipe cannot put in water If the drain water was discharged to ditch directly the drain pipe must be upward bent into a U type water seal to avoid odor into the...

Page 22: ...itioners The wiring of 71T1 to 160T1 indoor unit please refer to Fig 11 3 and Fig 11 4 is the wiring for 200T1 250T1 and 280T1 indoor unit Table 11 1 Capacity KW 71 80 90 112 140 160 200 250 280 Power...

Page 23: ...DOOR COMM BUS POWER INPUT Y G For 200 250 280 models TA A T1 A T2 A T2B A XP4 XS4 XP5 XS5 OLD DISPLAY BOARD WIRE CONTROLLER DC FAN TA B T1 B T2 B T2B B WHITE BLACK CN23 CN24 CN25 CN26 CN15 CN10 CN16 W...

Page 24: ...ll distribute different addresses for indoor units automatically When V4 outdoor unit set the code to be found address non automatically all the indoor units must set the system addresses by remote co...

Page 25: ...ing SW6 ON 1234 l reserved For B SYSTEM SW 1 Difinition SW 2 Difinition SW3 ON 1 2 l 00 means the time ofstopping TERMAL fan is 4 mintues SW3 ON 1 2 l 01 means the time ofstopping TERMAL fan is 8 mint...

Page 26: ...rtfunction J2 l r eserve d 0 1 Definition ON l means 0 ON l means 1 Please adjust the code ENC1 to the suitable position both system A and B should be adjusted for 200T1 250T1 and 280T1 indoor unit Th...

Page 27: ...rement install the remotecontroller frame where the remote controller s signal can reach the indoor unit smoothly Test operation Set the air conditioner under the mode of COOLING with the remotecontro...

Page 28: ......

Reviews: