background image

installation manual

 

17

 

 

● 

Fix the main body and the outside frame with the fix board of 

waist- shape hole (in two places).

 

 

Hang one side of the fix board of the waist-shaped hole on the

 

① 

hook of the main body.

 

 

② 

Tighten the other side of the board with screw to the outside 
frame.

 

 

③ 

Cut off the surplus part of the board with pliers.

 

Bend the top of the broken end.

 

 

 

When hanging up  the outside frame with the fix board  of waist-
shaped  hole  and  the  belt,  stick  the  outside  frame  tightly  to  the 
ceiling and fix it.

 

 

 

 

Fig.7-16

 

● 

Install the inner frame on the outside frame (the inverse sequence 
of unloading the inner frame).

 

 

Fig.7-17

 

 

Connect  the remote-control receiver with the indoor  unit signal 
wires and fix it.

 

 

 

 

● 

Install remote controller.

 

● 

Keep the connecting pipe dry, and do not let moisture in 
during  installation.

 

 

The Procedure of Connecting Pipes

 

Measure the necessary length of the connecting pipe, and make 
it by the following way.

 

 

● 

Connect the indoor unit at first, then the outdoor unit.

 

① 

Bend the tubing in proper way. Don’t harm them.

 

② 

Daub the surfaces of the flare pipe and the joint nuts with frozen 

oil, and wrench  it for 3~4rounds with  hands before fasten the 
flare nuts. (Refer to 

Fig.8-1

)

 

③ 

Be sure to use two wrenches simultaneously when you connect 
or disconnect the pipes.

 

 

● 

The stop valve of the outdoor unit should be closed absolutely 
(as original state). Every time you connect it, first loosen the nuts 
at the part of stop valve, then connect the flare pipe immediately 
(in 5 minutes). If the nuts have been loosened for a long time, 
dusts and other impurities may enter the pipe system and may 
cause malfunction later. So please expel the air out of the pipe 
with refrigerant before connection.

 

 

● 

Expel the air (refer to the “Expel The Air”) after connecting the 
refrigerant pipe with the indoor unit and the outdoor unit. Then 
fasten the nuts at the repair-points.

 

 

Notices For Benable pipe.

 

 

● 

The bending angle should not exceed 90

 

● 

Bending position is preferably in the bendable pipe. The larger 
the better it is .

 

 

● 

Do not bend the pipe more than three times.

 

 

Bend the connecting pipe of small wall thickness.

 

 

● 

Cut out a desired concave at the bending part of the insulating 
pipe.

 

 

● 

Then expose the pipe (cover it with tapes after bending).

 

 

● 

To prevent collapsing of deforming, please bend the pipe at its 
biggest radius.

 

 

● 

Use bender to get a small radius pipes.

 

 

Use the market brass pipe.

 

Be sure to use the same insulating materials when you buy the 
brass pipe. (More than 9mm thick)

 

8.

 

INSTALL THE CONNECTING PIPE 

 

Use frozen oil

 

 

Check  whether  the  height  drop  between  the  indoor  unit  and 
outdoor unit, the length of refrigerant pipe, and the number of 
the bends meet the following requirements:

 

 

● 

The max height drop and The length of refrigerant pipe deponding 
on the outdoor unit.(If  the height drop is more than 10m, you 
had better put the outdoor unit over above the indoor unit.) 

 

● 

The number bends fewer than 15. 

 

● 

Do not let air, dust, or other impurities fall in the pipe system 
during the time of installation. 

 

● 

The connecting pipe should not be installed until the indoor and 
outdoor units have been fixed already. 

 
 
 
 
 
 

 

Bend the pipe with thumb

 

 

 
 
 
 
 

 

Make the ends 
straight

 

 

Fig.8-1

 

 
 
 
 
 
 

 

Fig.8-2

 

 
 
 

 

Fig.8-3

 

  

NOTE 

 

Hook

 

Waist-shaped hole 
fixed board

 

Outside frame

 

Bend

 

Air passage

 

(Reverse side)

 

Outside frame

 

Air inlet

 

Inside frame

 

  

NOTE 

 

 
 

 

  

 

Summary of Contents for KPDHF-71 DN3.0

Page 1: ...0 DN3 0 KPDHF 160 DN3 0 KPDHF 200 DN3 0 KPDHF 250 DN3 0 KPDHF 280 DN3 0 The Digital Scroll and DC AC Inverter share the same indoor units Thank you very much for purchasing our air conditioner Before...

Page 2: ...MD14I 041FW DZ2 16100101A01132...

Page 3: ...nce and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do n...

Page 4: ...ive and negative poles are in right positions when loading batteries 4 INDOOR UNIT INSTALLATION Installing 10 Hanging Screw Bolts 4 Bolts Please refer to the following figure for the distance measurem...

Page 5: ...eel refer to Fig 4 4 Overhanging the indoor unit Fig 4 4 Fig 4 7 Overhang the indoor unit onto the hanging screw bolts with block Position the indoor unit in a flat level by using the level indicator...

Page 6: ...ONNECTION SAFETY DRAIN CONNECTING PIPE AIR OUTLET 255 33 65 722 65 Fig 4 9 14 16KW 135 930 88 Unit mm PLASTIC COVER 68 24 46 ELECTRICAL CONTROL BOX 4 12 25OBLONGSUSPENTIONBOLTHOLES AIR INTAKE CONNECTI...

Page 7: ...w as Fig 4 11 SafetyDrainTray Fig 4 12 2 Remove the all 11 screw from fixed Safety Drain Tray and then take off the tray as figure showed in Fig 5 11 3 Take off the tray along the direction of the arr...

Page 8: ...all 4 bolts from reinforced panel and take off the panel 3 Refer to Fig 4 13 remove all 4 bolts from fan assembly see Fig 4 14 according to which orders to take off the fanassembly 4 Refer to Fig 4 1...

Page 9: ...11 screw from fixed Safety Drain Tray and then take off the tray as figure showed inFig 4 16 3 Take off the tray along the direction of the arrow show in Fig 4 16 4 Clean the tray and evaporator 5 Re...

Page 10: ...m fan assembly see Fig 4 18 according to which orders to take off the fan assembly 3 Refer to Fig 4 18 horizontal pushing the fan assembly until it cannot not move any further and then lift up slightl...

Page 11: ...nnection 9 52 3 8 Refrigerant pipe flared connection 16 5 8 Air intake duct flange 1270 Connecting point of drain pipe 43 125 100 Air intake 936 200 Fig 4 19 The method of installation adopt following...

Page 12: ...onfirm that there is enough room for installation and mainte nance Maintenance roomage Maintenance roomage motor assembly bottom cover plate screw Confirm the minimum drain tilt is 1 100 or more check...

Page 13: ...ut dust filter dust adherent on the air heat exchanger may cause failure and water leak Key points of duct connection Canvas tie in Canvas tie in Fig 7 1 Other assemblies should be prepared on spot ex...

Page 14: ...12 9KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 7 Fig 7 5 11 2KW model fan curve the static pressure refer to Table 12 2 Middle fan speed Fig 7 6 Hig...

Page 15: ...installation manual 13 Middle fan speed 14KW model fan curve the static pressure refer to Table 12 2 High fan speed Low fan speed Fig 7 9 Fig 7 10 Middle fan speed Fig 7 11 Fig 7 12...

Page 16: ...installation manual 14 Low fan speed Middle fan speed Fig 7 13 16KW model fan curve the static pressure refer to Table 12 2 Low fan speed Fig 7 15 High fan speed Fig 7 16 Fig 7 14...

Page 17: ...20KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 19 Middle fan speed Fig 7 17 25KW 28KW model fan curve the static pressure refer to Table 12 2 High fan...

Page 18: ...1 Hang the outside frame on the main body with face down 4 places at 4 corners Hang the belt on the hook of the main body Low fan speed Fig 7 22 The signal wire of the remote control receiver must be...

Page 19: ...urities may enter the pipe system and may cause malfunction later So please expel the air out of the pipe with refrigerant before connection Expel the air refer to the Expel The Air after connectingth...

Page 20: ...pipe cutter Insert a flare nut into a pipe and flare the pipe lean crude burr 9 2 Check The Leakage Fig 9 1 Fasten the nut Put the connecting tubing at the proper position wrench the nuts with hands...

Page 21: ...l should be more than 50mm and the drain pipe cannot put in water If the drain water was discharged to ditch directly the drain pipe must be upward bent into a U type water seal to avoid odor into the...

Page 22: ...itioners The wiring of 71T1 to 160T1 indoor unit please refer to Fig 11 3 and Fig 11 4 is the wiring for 200T1 250T1 and 280T1 indoor unit Table 11 1 Capacity KW 71 80 90 112 140 160 200 250 280 Power...

Page 23: ...DOOR COMM BUS POWER INPUT Y G For 200 250 280 models TA A T1 A T2 A T2B A XP4 XS4 XP5 XS5 OLD DISPLAY BOARD WIRE CONTROLLER DC FAN TA B T1 B T2 B T2B B WHITE BLACK CN23 CN24 CN25 CN26 CN15 CN10 CN16 W...

Page 24: ...ll distribute different addresses for indoor units automatically When V4 outdoor unit set the code to be found address non automatically all the indoor units must set the system addresses by remote co...

Page 25: ...ing SW6 ON 1234 l reserved For B SYSTEM SW 1 Difinition SW 2 Difinition SW3 ON 1 2 l 00 means the time ofstopping TERMAL fan is 4 mintues SW3 ON 1 2 l 01 means the time ofstopping TERMAL fan is 8 mint...

Page 26: ...rtfunction J2 l r eserve d 0 1 Definition ON l means 0 ON l means 1 Please adjust the code ENC1 to the suitable position both system A and B should be adjusted for 200T1 250T1 and 280T1 indoor unit Th...

Page 27: ...rement install the remotecontroller frame where the remote controller s signal can reach the indoor unit smoothly Test operation Set the air conditioner under the mode of COOLING with the remotecontro...

Page 28: ......

Reviews: