Connect the joint of the charge hose with the vacuum pump. 

● 

Open the Lo-lever of the manifold valve completely. 

● 

Turn on the vacuum pump. At the beginning of pumping, 
loosen the maintenance terminator nut of stop valve B a little 
to check whether the air comes in (the sound of the pump 
changes, and the indicator of compound meter turns below 
zero). Then fasten the nut. 

● 

When the  pumping  has finished, close the  Lo-lever  of the 
manifold valve completely and turn off the vacuum pump. 

● 

When you have pumped for over 15 minutes, please confirm 
that the indicator of multimeter is on -1.0X105Pa  (-76cmHg) 

● 

Loosen and remove the quadrangle cover of stop valves A 
and B to open stop valve A and B completely, then fasten 
them. 

● 

Disassemble the charge hose from the repair-mouth of stop 
valve A, and fasten the nut. 

 

Manifold valve

 

 

 

 

The drain pipe of indoor unit must be heat insulated, or it will 
condense dew, as well as the connections of the indoor unit.

 

 

Hard PVC binder must be used for pipe connection, and make 
sure there is no leakage.

 

 

With the connection part to the indoor unit, please be noted not 
to impose pressure on the side of indoor unit pipes.

 

 

When the declivity of the drain pipe downwards is over 1/100, 
there should not be any winding.

 

 

The  total  length  of  the  drain  pipe  when  pulled  out  traversely 
shall not exceed 20m, when the pipe is over long, a prop stand 
must be installed to prevent winding.

 

The height difference between drain pipe end to ground or drain 
channel should be more than 50mm, and the drain pipe cannot 
put in water. If the drain water was discharged to ditch directly, 
the drain pipe must be upward bent into a U type water seal to 
avoid odor into the interior through the drain pipe.

 

 

If the negative pressure of drain pan outlet is high, there must 
be a water elbow in drain pipe to avoid poor drain or blow water 
for negative pressure. Please install the water elbow as figure

 

4.4 shown, each unit should install a water elbow. There should 
be a plug in water elbow for convenient cleaning.

 

 

Refer to the figures on the right for the installation of the pipes.

 

 

 

 

 

Fig.9-5

 

 
 

1.5M~2M

 

 
 

 

All  the  stop  valves  should  be  opened  before  test  operation. 
Each air conditioner has two stop valves of different sizes on 
the  side  of  the  outdoor  unit  which  operate  as  Lo-stop  value 
respectively. (Refer to 

Fig.9-6

)

 

 
 
 
 

 

Put as deep as possible 

(about 10mm)

 

 

Fig.10-1

 

 
 
 

 
 

 

Valve stem

 

 

Fig.9-6

 

 

 

Downward declivity

 

lower than 1/100 

VP30

 

 
 

 

Fig.10-2

 

 

10.

 

CONNECT THE DRAIN PIPE 

Install indoor unit drain pipe

 

The outlet has PTI screw bread, For 71T1 to 160T1 indoor unit, 
please use sealing materials and pipe sheath (fitting) when 
connecting PVC pipes. For  200T1 to 280T1 indoor unit, please 
use Water connecting pipe 

and Adhesive tape for seal 

when connecting 

drain pipes.

 

 

H

 

H: 2''(50mm) or more.

 

H

 

 

 

Fig.10-3

 

 

Caution:  While  connecting  the  drain  pipe,  please  use  the  drain 
pipe  connect  to  the  secondary  water  holder  simultaneously,  for 
avoiding there are little condensate water deposit in the unit when 
the machine is running under the high humidity working condition.

 

CAUTION

 

Flare nut

 

Stopper

 

 

Cap

 

Valve body

 

Multi-meter

 

Pressure meter

 

-76 cmHg

 

Hi-lever

 

Lo-lever

 

Charge hose

 

Charge hose

 

Vacuum pump

 

Lo-lever

 

Summary of Contents for KPDHF-71 DN3.0

Page 1: ...0 DN3 0 KPDHF 160 DN3 0 KPDHF 200 DN3 0 KPDHF 250 DN3 0 KPDHF 280 DN3 0 The Digital Scroll and DC AC Inverter share the same indoor units Thank you very much for purchasing our air conditioner Before...

Page 2: ...MD14I 041FW DZ2 16100101A01132...

Page 3: ...nce and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do n...

Page 4: ...ive and negative poles are in right positions when loading batteries 4 INDOOR UNIT INSTALLATION Installing 10 Hanging Screw Bolts 4 Bolts Please refer to the following figure for the distance measurem...

Page 5: ...eel refer to Fig 4 4 Overhanging the indoor unit Fig 4 4 Fig 4 7 Overhang the indoor unit onto the hanging screw bolts with block Position the indoor unit in a flat level by using the level indicator...

Page 6: ...ONNECTION SAFETY DRAIN CONNECTING PIPE AIR OUTLET 255 33 65 722 65 Fig 4 9 14 16KW 135 930 88 Unit mm PLASTIC COVER 68 24 46 ELECTRICAL CONTROL BOX 4 12 25OBLONGSUSPENTIONBOLTHOLES AIR INTAKE CONNECTI...

Page 7: ...w as Fig 4 11 SafetyDrainTray Fig 4 12 2 Remove the all 11 screw from fixed Safety Drain Tray and then take off the tray as figure showed in Fig 5 11 3 Take off the tray along the direction of the arr...

Page 8: ...all 4 bolts from reinforced panel and take off the panel 3 Refer to Fig 4 13 remove all 4 bolts from fan assembly see Fig 4 14 according to which orders to take off the fanassembly 4 Refer to Fig 4 1...

Page 9: ...11 screw from fixed Safety Drain Tray and then take off the tray as figure showed inFig 4 16 3 Take off the tray along the direction of the arrow show in Fig 4 16 4 Clean the tray and evaporator 5 Re...

Page 10: ...m fan assembly see Fig 4 18 according to which orders to take off the fan assembly 3 Refer to Fig 4 18 horizontal pushing the fan assembly until it cannot not move any further and then lift up slightl...

Page 11: ...nnection 9 52 3 8 Refrigerant pipe flared connection 16 5 8 Air intake duct flange 1270 Connecting point of drain pipe 43 125 100 Air intake 936 200 Fig 4 19 The method of installation adopt following...

Page 12: ...onfirm that there is enough room for installation and mainte nance Maintenance roomage Maintenance roomage motor assembly bottom cover plate screw Confirm the minimum drain tilt is 1 100 or more check...

Page 13: ...ut dust filter dust adherent on the air heat exchanger may cause failure and water leak Key points of duct connection Canvas tie in Canvas tie in Fig 7 1 Other assemblies should be prepared on spot ex...

Page 14: ...12 9KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 7 Fig 7 5 11 2KW model fan curve the static pressure refer to Table 12 2 Middle fan speed Fig 7 6 Hig...

Page 15: ...installation manual 13 Middle fan speed 14KW model fan curve the static pressure refer to Table 12 2 High fan speed Low fan speed Fig 7 9 Fig 7 10 Middle fan speed Fig 7 11 Fig 7 12...

Page 16: ...installation manual 14 Low fan speed Middle fan speed Fig 7 13 16KW model fan curve the static pressure refer to Table 12 2 Low fan speed Fig 7 15 High fan speed Fig 7 16 Fig 7 14...

Page 17: ...20KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 19 Middle fan speed Fig 7 17 25KW 28KW model fan curve the static pressure refer to Table 12 2 High fan...

Page 18: ...1 Hang the outside frame on the main body with face down 4 places at 4 corners Hang the belt on the hook of the main body Low fan speed Fig 7 22 The signal wire of the remote control receiver must be...

Page 19: ...urities may enter the pipe system and may cause malfunction later So please expel the air out of the pipe with refrigerant before connection Expel the air refer to the Expel The Air after connectingth...

Page 20: ...pipe cutter Insert a flare nut into a pipe and flare the pipe lean crude burr 9 2 Check The Leakage Fig 9 1 Fasten the nut Put the connecting tubing at the proper position wrench the nuts with hands...

Page 21: ...l should be more than 50mm and the drain pipe cannot put in water If the drain water was discharged to ditch directly the drain pipe must be upward bent into a U type water seal to avoid odor into the...

Page 22: ...itioners The wiring of 71T1 to 160T1 indoor unit please refer to Fig 11 3 and Fig 11 4 is the wiring for 200T1 250T1 and 280T1 indoor unit Table 11 1 Capacity KW 71 80 90 112 140 160 200 250 280 Power...

Page 23: ...DOOR COMM BUS POWER INPUT Y G For 200 250 280 models TA A T1 A T2 A T2B A XP4 XS4 XP5 XS5 OLD DISPLAY BOARD WIRE CONTROLLER DC FAN TA B T1 B T2 B T2B B WHITE BLACK CN23 CN24 CN25 CN26 CN15 CN10 CN16 W...

Page 24: ...ll distribute different addresses for indoor units automatically When V4 outdoor unit set the code to be found address non automatically all the indoor units must set the system addresses by remote co...

Page 25: ...ing SW6 ON 1234 l reserved For B SYSTEM SW 1 Difinition SW 2 Difinition SW3 ON 1 2 l 00 means the time ofstopping TERMAL fan is 4 mintues SW3 ON 1 2 l 01 means the time ofstopping TERMAL fan is 8 mint...

Page 26: ...rtfunction J2 l r eserve d 0 1 Definition ON l means 0 ON l means 1 Please adjust the code ENC1 to the suitable position both system A and B should be adjusted for 200T1 250T1 and 280T1 indoor unit Th...

Page 27: ...rement install the remotecontroller frame where the remote controller s signal can reach the indoor unit smoothly Test operation Set the air conditioner under the mode of COOLING with the remotecontro...

Page 28: ......

Reviews: