8.6.9 Installation of multi-module water system pipeline
Multi-module combination installation involves special design of the unit, so relevant explanation is given as follows.
8.6.9.1 Installation mode of multi-module combination water system pipeline
No.n module
No.(n-1) address
No.1 module
No.(n-1) module
No.(n-2) address
No.0 address
Pump
Drill a hole at the marked
position and move the total
water outlet temperature
sensor of No. 0 address unit
to this position.
Fig.8-34 Installation of multi-module (no more than 16 modules)
CAUTION
KEM-30 DNS3 and KEM-60 DNS3 can be connected in the same water system, while KEM-90 DNS3 can not be connected with other
models.
8.6.9.2 Table of diameter parameters of main inlet and outlet pipes
Table 8-15
Cooling capacity(kW)
Total inlet and outlet water
pipe inside nominal diameter
15≤Q≤30
DN40
30<Q≤90
DN50
90<Q≤130
DN65
130<Q≤210
DN80
210<Q≤325
DN100
325<Q≤510
DN125
510<Q≤740
DN150
740<Q≤1300
DN200
1300<Q≤2080
DN250
CAUTION
Please pay attention to the following items when installing multiple modules:
● Each module corresponds to an address code which cannot be repeated.
● Main water outlet temperature sensor and auxiliary electric heater are under control of the main module.
● The unit can be started up through the wired controller only after all addresses are set and the aforementioned items are determined. The
wired controller is ≤500m away from the outdoor unit.