47
12. APPLICABLE MODELS AND MAIN PARAMETERS
Table 12-1
Model
KEM-30 DNS3
KEM-60 DNS3
KEM-90 DNS3
Cooling capacity
kW
27
55
82
Heating capacity
kW
31
61
90
Standard cooling input
kW
10.8
22
36.8
Cooling rated current
A
16.7
33.9
60
Standard heating input
kW
10.5
20.3
32.8
Heating rated current
A
16.2
31.3
53.5
Power supply
380-415V 3N ~ 50
Refrigerant
Type
R410A
Charging volume kg
10.5
17.0
27.0
Water pipe system
Water Folw volume
(m
3
/h)
5.0
9.8
15
Hydraulic resistance lose
kPa
80
50
75
Water side heat
exchanger
Plate heat exchanger
Max. pressure MPa
1.0
Min. pressure MPa
0.05
Inlet and outlet pip e
diameter
DN40
DN50
Air side heat exchanger
Type
Fin coil model
Air flow volume
(m
3
/h)
12500
24000
38000
Outline dimension
N.W. of the unit
L (mm)
1870
2220
3220
W (mm)
1000
1055
1095
H (mm)
1175
1325
1513
Net Weight
kg
300
480
710
Operation Weight
kg
310
490
739
Packing dimension
L×W×H (mm)
1910×1035×1225
2250×1090×1370
3275×1130×1540