40
31
PA
Cooling return water temperature too high
Recovered upon failure recovery
32
Pb
Winter antifreeze protection
Recovered upon failure recovery
33
PC
Evaporator pressure low in cooling
Recovered upon failure recovery
35
PE
Cooling evaporator low-temperature
antifreeze protection (recovered through button)
Recovered upon failure recovery
37
PH
Heating T4 too high temperature protection
Recovered upon failure recovery
38
PL
Tfin module too high temperature protection
Protection occurs 3 times in 100 minutes
and the failure can be recovered by power
disconnection only.
40
PU
1PU-->DC fan A module protection
Recovered upon failure recovery
2PU-->DC fan B module protection
Recovered upon failure recovery
41
H0
1H0: IPM module communication failure
Recovered upon failure recovery
2H0: IPM module communication fault
Recovered upon failure recovery
42
H1
Over/under-voltage protection
Recovered upon failure recovery
45
H4
1H4: PP protection occurs 3 times in 60 minutes (power failure recovery)
Reserved
2H4: PP protection occurs 3 times in 60 minutes (power failure recovery)
Reserved
47
H6
1H6: A system bus voltage failure (PTC)
Recovered upon failure recovery
2H6: B system bus voltage failure (PTC)
Recovered upon failure recovery
72
Fb
Pressure sensor failure
Recovered upon failure recovery
74
Fd
Air suction temperature sensor failure
Recovered upon failure recovery
76
FF
1FF DC fan A failure
Protection occurs 3 times in 20 minutes
and the failure can be recovered by power
disconnection only.
2FF DC fan B failure
Protection occurs 3 times in 20 minutes
and the failure can be recovered by power
disconnection only.
79
FP
DIP inconsistency of multiple water pumps
Power failure recovery required
101
L0
Inverter module protection
Recovered upon failure recovery
102
L1
DC bus low voltage protection
Recovered upon failure recovery
103
L2
DC bus high voltage protection
Recovered upon failure recovery
105
L4
MCE failure
Recovered upon failure recovery
106
L5
zero speed protection
Recovered upon failure recovery
108
L7
phase sequence error
Recovered upon failure recovery
109
L8
Compressor frequency variation more than 15Hz within one second
protection
Recovered upon failure recovery
110
L9
Actual compressor frequency differs from target frequency by more than
15Hz protection
Recovered upon failure recovery
146
dF
Defrosting prompt
Recovered upon failure recovery