41
Table 11-2 KEM-90 DNS3
Error
No.
Code
reason
note
1
E0
Main control parameter memory EPROM failure
Recovered upon failure recovery
2
E1
Phase sequence failure of main control board check
Recovered upon failure recovery
3
E2
Main control and wired control communication failure
Recovered upon failure recovery
4
E3
Total water outlet temperature sensor failure (main unit valid)
Recovered upon failure recovery
5
E4
Unit water outlet temperature sensor failure
Recovered upon failure recovery
6
E5
1E5 condenser tube temperature sensor T3A failure
Recovered upon failure recovery
2E5 condenser tube temperature sensor T3B failure
Recovered upon failure recovery
8
E7
Ambient temperature sensor failure
Recovered upon failure recovery
9
E8
Power supply phase sequence protector output failure
(reserved)
Recovered upon failure recovery
10
E9
Water flow detection failure (recovered through button)
Protection occurs 3 times in 60 minutes and the failure
can be recovered by power disconnection only.
12
Eb
1Eb-->Taf1 cooling evaporator low-temperature antifreeze
protection sensor failure
Recovered upon failure recovery
2Eb-->Taf2 cooling evaporator low-temperature antifreeze
protection sensor failure
Recovered upon failure recovery
13
EC
auxiliary unit module reduction
Recovered upon failure recovery
14
Ed
1Ed-->A system discharge temperature sensor failure
Recovered upon failure recovery
2Ed-->B system discharge temperature sensor failure
Recovered upon failure recovery
15
EE
1EE EVI plate heat exchanger refrigerant temperature T6A
sensor failure
Recovered upon failure recovery
2EE EVI plate heat exchanger refrigerant temperature T6B
sensor failure
16
EF
Unit water return temperature sensor failure
Recovered upon failure recovery
17
EH
System self-check failure alarm
Recovered upon failure recovery
19
EP
Discharge temperature sensor failure alarm
Recovered upon failure recovery
20
EU
Tz/7 Coil final outlet temperature sensor error
Recovered upon failure recovery
21
P0
System high-pressure protection or discharge temperature
protection
Protection occurs 3 times in 60 minutes and the failure
can be recovered by power disconnection only.
22
P1
System low pressure protection
Protection occurs 3 times in 60 minutes and the failure
can be recovered by power disconnection only.
23
P2
Tz/7 Coil final outlet temperature too high
Recovered upon failure recovery
25
P4
System A current protection
Protection occurs 3 times in 60 minutes and the failure
can be recovered by power disconnection only.
26
P5
System B current protection
Protection occurs 3 times in 60 minutes and the failure
can be recovered by power disconnection only.
27
P6
Module failure
Protection occurs 3 times in 60 minutes and the failure
can be recovered by power disconnection only.
28
P7
High temperature protection of system condenser
Protection occurs 3 times in 60 minutes and the failure
can be recovered by power disconnection
30
P9
Water inlet and outlet temperature difference protection
Protection occurs 3 times in 60 minutes and the failure
can be recovered by power disconnection
32
Pb
Winter antifreeze protection
Recovered upon failure recovery
33
PC
Evaporator pressure low in cooling
Recovered upon failure recovery
35
PE
Cooling evaporator low temperature antifreeze protection
Recovered upon failure recovery
37
PH
Heating T4 too high temperature protection
Valid for heating
38
PL
Tfin module too high temperature protection
Protection occurs 3 times in 100 minutes and the failure
can be recovered by power disconnection only.
40
PU
1PU-->DC fan A module protection
Recovered upon failure recovery
2PU-->DC fan B module protection
Recovered upon failure recovery
3PU-->DC fan C module protection
Recovered upon failure recovery
46
H5
pressure too high or low
Recovered by power disconnection
50
xH9
Drive model not matched
x indicates the compressor: 1 indicates compressor A,
and 2 indicates compressor B.