background image

 

Original instruction in English                                                                                                          

 

 

REV 

02 

Date 

December 2018 

Supersedes 

D-EIMWC003H02-18_01EN 

 

 

 

 
 
 

WATER-COOLED 

WATER 

CHILLERS 

WITH 

VARIABLE 

SPEED 

COMPRESSOR 

 

EWWD - VZ 
EWWH - VZ 

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Installation, maintenance and operating manual 

D-EIMWC003H02-18_02EN 

 

Summary of Contents for EWWD VZ

Page 1: ...ion in English REV 02 Date December 2018 Supersedes D EIMWC003H02 18_01EN WATER COOLED WATER CHILLERS WITH VARIABLE SPEED COMPRESSOR EWWD VZ EWWH VZ Installation maintenance and operating manual D EIM...

Page 2: ...or shut off valves 19 2 15 Electrical connections 19 2 16 Phase imbalance 19 2 17 Control circuit 20 3 OPERATION 20 3 1 Operator s responsibilities 20 3 2 Unit description 21 3 3 Cooling cycle descrip...

Page 3: ...applied to the unit 4 Figure 2 Description of the labels applied to the electric panel 6 Figure 3 Lifting instructions 11 Figure 4 Unit positioning 12 Figure 5 Condenser control scheme with cooling to...

Page 4: ...D EIMWC003H02 18_02EN 4 34 Figure 1 Description of the labels applied to the unit Single circuit unit...

Page 5: ...R solenoid valve circ 1 1 8 VR 5 Evaporator entering water temperature sensor 17 High pressure switch 6 Air purge 18 Discharge temperature sensor 7 Water drain 19 Oil Pressure Transducer 8 Liquid line...

Page 6: ...unit Identification of labels 1 Manufacturer s logo 8 Lifting instructions 2 Electricity warning 9 Refrigerant 3 Shutoff valve position 10 W012 Symbol 4 Wire tightness check 11 Attention Closed Valve...

Page 7: ...e refrigerant leaks 13 disable the unit from the mains using the main switch before opening the control panel 14 check that the unit has been grounded correctly before starting it 15 install the machi...

Page 8: ...e screw compressor and adjustment inverters are designed and constructed to cool and or heat buildings or industrial processes Daikin technicians specifically trained for this purpose must start the f...

Page 9: ...azing or similar activity and then only provided the refrigerant concentration is monitored and adequate ventilation is ensured Such open flames shall not be left unattended A remote switching emergen...

Page 10: ...0 303 kg m3 0 07575 kg m3 16500 ppm All electrical equipment not only the refrigerating system shall be selected to be suitable for use in the zones identified in the risk assessment Electrical equipm...

Page 11: ...n pads optional are shipped separately Make sure these items if required are delivered with the unit Use extreme caution when handling the unit to prevent damage to the control panel and the refrigera...

Page 12: ...prevent refrigerant accumulation inside that can deprive air of the right oxygen content that can cause asphyxiation In this regard we recommend the application of harmonized standard EN378 3 Safety a...

Page 13: ...freezing The flow switch must not be used as a machine control system The absence of the flow switch on the evaporator water connection voids the warranty for frost damage The evaporator and condenser...

Page 14: ...f untreated water can result in corrosion erosion mud fouling and formation of algae Daikin Applied Europe is not liable for equipment damage or malfunction due to a lack of a water treatment or water...

Page 15: ...and high condenser inlet water temperature may be inhibited Glycol must be used for all applications with the evaporator outlet fluid below 4 C The maximum permissible water temperature in the evapor...

Page 16: ...C Ref 2c standard unit opt 174 Low Brine Limit for Propylene Glycol ELWT 8 C Ref 3 standard unit opt 111 High temperatures kit Ref 4a standard unit opt 08 Brine opt 111 high temperature kit Limit for...

Page 17: ...5 lt kW Process 6 6 lt kW 5 0 lt kW Variable capacity 6 6 lt kW 5 0 lt kW Calculation example Cooling capacity at 100 670 kW Minimum system volume for conditioning 670 x 3 3 2211 lt Minimum system vol...

Page 18: ...re should not be less than 20 C at full water tower flow rate If the water temperature must be lower even the water flow must be reduced proportionately To modulate the water flow to the condenser ins...

Page 19: ...onsible for connecting the safety valve to the purge pipe and pipe dimensioning In this regard refer to the harmonized standard EN13136 to dimension the drain pipes to be connected to the safety valve...

Page 20: ...tor becomes familiar with the equipment before operating the machine In addition to reading this manual the operator should study the operation manual and the wiring diagram supplied with the unit to...

Page 21: ...ased to the condensation water which heats accordingly The condensed fluid at saturation temperature passes through the sub cooling section where it yields heat to further increase cycle efficiency Th...

Page 22: ...control protects the compressor from any operating faults The oil filter must be replaced within the first 500 hours of compressor operations The electronic controller generates an alarm for high oil...

Page 23: ...te that all units are also provided with the Control Manual Figure 7 Unit interface 3 3 8 Safeties for each refrigerant circuit High pressure pressure switch Motor cooling High compressor delivery tem...

Page 24: ...thermistors the controller is able to constantly monitor winding temperature and stop the corresponding compressor in the event that the temperature exceeds the safety value Repeated interventions of...

Page 25: ...tem the heat transfer fluid should be checked for the possible presence of refrigerant After any repair work the safety devices for example refrigerant detectors and mechanical ventilation systems sho...

Page 26: ...f compressors installed on the machine The valves are managed and controlled by the main electronic controller that optimizes the flow of refrigerant gas to the evaporator according to machine operati...

Page 27: ...Typical single circuit cooling circuit Fig 7 Typical dual circuit cooling circuit Legend 1 Compressor 15 Oil injection valve 2 Delivery valve optional 16 Oil injection solenoid valve 3 Oil Condenser S...

Page 28: ...0 5 and 4 C d The difference between condensing temperature and condenser outlet water temperature is between 1 and 3 C 5 Make sure the indicator on the liquid tube is full If one of these parameters...

Page 29: ...ed Europe Spa cannot be held liable for damage caused by untreated or improperly treated water 4 5 2 Seasonal start up Annual start up is a good time to assess motor winding ground resistance A semi a...

Page 30: ...ntative technical staff a Oil Analysis have to be performed each year or every 5000 hours of operation whichever shall first occur b Change the oil filter if p 2 bar c Check water temperature entering...

Page 31: ...operable Water system operated and flow balanced to meet unit design requirements Electrical Power leads connected to unit main terminal block Power leads have been checked for proper electrical phasi...

Page 32: ...g instructions Any refrigerant charge for each circuit 1 2 3 added during commissioning the total refrigerant charge 1 2 3 calculate the greenhouse gas emission with the following formula 1000 Use the...

Page 33: ...rdance with local laws regarding disposal and if in scope with the national laws implementing the Directive 2012 19 EU RAEE Batteries and electrical components must be sent to specific waste collectio...

Page 34: ...contained herein are liable to change without notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A cannot be held liable for direct or indirect damage in the bro...