background image

D-EIMWC003H02-18_02EN - 21/34 

 

It is strongly recommended to perform installation and maintenance with other people.  
In case of accidental injury or unease, it is necessary to: 

Keep calm. 

Press the alarm button if present in the installation site. 

Move the injured person to a warm place far from the unit and in place him or her in the recovery position. 

Immediately contact any emergency personnel in the building or the call the Emergency Services. 

Wait until emergency personnel arrive and do not leave the injured person alone. 

 

3.2 

Unit description 

The machine is made up of a latest generation, high efficiency, new VVR series single screw compressor, flooded shell and 
tube evaporator with the refrigerant outside the tubes and the water to be cooled flowing inside the tube. 
A  shell  and  tube  condenser  where  the  refrigerant  condenses  outside  the  tubes  while  the  cooling  water  flows  inside  of  the 
high-efficiency tubes. 
The compressor is of the mono screw semi-hermetic type and utilizes the suction gas coming from the evaporator to cool the 
motor and permit the optimum operations in all machine load conditions. The compressor, controlled by inverters, changes 
its  cooling  load  according  to  the  rotational  speed  decided  by  the  controller.  In  this  way  the  machine  perfectly  adapts  to 
system operating conditions to maximize performance. 
The oil injection lubrication system, in addition to allowing normal moving part lubrication, also seals the screw ensuring gas 
compression, without the aid of an external oil pump. 
The cooling circuit also installs an electronic expansion valve that, in addition to managing the level of refrigerant in the heat 
exchangers and guaranteeing the correct operation of the compressor, also manages the PUMP-DOWN function. 
All  the  described  components  are  managed  by  an  innovative  microprocessor  control  system  that,  by  monitoring  all  the 
machine operating parameters, optimizes operations. 
A diagnostic system helps the operator in identifying alarm and fault causes. 

 

Before  starting  the  compressors  ensure  that  all  valves  are  open  and  the  closing  caps  are 
repositioned and tightened. 

 

3.3 

Cooling cycle description 

The low temperature refrigerant gas coming from the evaporator is sucked by the compressor and flows through the electric 
motor,  cooling  it.  It  is  subsequently  compressed  and  during  this  phase  the  refrigerant  mixes  with  the  oil,  injected  in  the 
compressor, from the separator. 
The high-pressure oil-refrigerant mixture is introduced inside the three-stage high efficiency oil separator which performs the 
separation. The oil deposited on the bottom of the separator is sent, by pressure difference, to the compressor again while 
the refrigerant separated from the oil is sent to the condenser. 
The  refrigerant  fluid  inside  the  condenser,  which  crosses  the  heat  exchanger  pipes  in  countercurrent,  de-superheats  and 
starts  to  condense.  The  de-superheating  heat  and  condensation  is  released  to  the  condensation  water  which  heats 
accordingly. 
The  condensed  fluid  at  saturation  temperature  passes  through  the  sub  cooling  section,  where  it  yields  heat  to  further 
increase cycle efficiency. The sub cooled fluid flows through the expansion device which, through a pressure drop, initiates 
the expansion process by vaporizing a part of the refrigerant liquid. 
The  result  at  this  point  is  a  mixture  of  liquid  and  gas  at  low  pressure  and  temperature,  which  is  introduced  into  the 
evaporator. 
The liquid-vapor refrigerant after being evenly distributed along the tube bundle exchanges heat with the water to be cooled 
by reducing the temperature, and it gradually changes state until being fully evaporated. 
Reaching the vapor state, it leaves the evaporator to be sucked by compressor again and restart the cycle. 

3.3.1 

Evaporator 

The evaporator is a flooded shell and tube type with water flowing inside the tubes and the gas refrigerant outside.  Normall y 
it  does  not  require  any  maintenance  and  service.  Should  a  tube  require  replacement,  the  old  tube  can  be  removed  and 
replaced. The water dome gasket must be replaced after tube cleaning and/or replacement. 

3.3.2 

Condenser 

The condenser is a shell and tube type with water flowing inside the tubes and the refrigerant outside. The condenser tubes 
are  externally  finned  and  expanded  on the  tube  plate.    A  sub  cooler  is  built into  the condenser  on  all  units.  Should a tube 
require  replacement,  the  old  tube  can  be  removed  and  replaced.  The  water  dome  gasket  must  be  replaced  after  tube 
cleaning and/or replacement. 

3.3.3 

Expansion valve 

The  expansion  valve  is  electrically  controlled  by  the  electronic  controller  by  means  of  a  specifically  designed  electronic 
board. A special algorithm designed for machines with flooded evaporators, manages the refrigerant flow to the evaporator 
according to machine operating parameters. In the event of blackout, the expansion valve automatically closes thanks to an 
electric power accumulation system placed inside the electronic control board (supercap) 

3.3.4 

Compressors 

The refrigeration compressor is the single screw type with the rotation shaft directly coupled to the electric motor. 
The vapor flows through the electric motor cooling the windings before entering the suction ports. Sensors able to constantly 
monitor  temperature  are  located  inside  the  motor  windings  to  fully  protect  the  motor  against  dangerous  overheating.  The 
thermistor and power terminals are housed within a terminal box placed above the motor housing. 
Moving  compressor  parts  that  effect  the  compression  consist  of  three  rotating  parts,  there  are  no  parts  in  eccentric  or 
reciprocating  movement  in  the  compressor.  The  essential  components  are  the  main  rotor  and  the  two  side  satellites  that 
perfectly  integrate  together.  The  compressor is  sealed  by  a  suitably  shaped  special synthetic  material  placed  between  the 
main rotor and the satellites. The main shaft on which both the motor and the main rotor are installed is supported by three 
ball  bearings.  This  system  is  both  statically  and  dynamically  balanced  before  assembly.  Two  large  closing  flanges  are 

Summary of Contents for EWWD VZ

Page 1: ...ion in English REV 02 Date December 2018 Supersedes D EIMWC003H02 18_01EN WATER COOLED WATER CHILLERS WITH VARIABLE SPEED COMPRESSOR EWWD VZ EWWH VZ Installation maintenance and operating manual D EIM...

Page 2: ...or shut off valves 19 2 15 Electrical connections 19 2 16 Phase imbalance 19 2 17 Control circuit 20 3 OPERATION 20 3 1 Operator s responsibilities 20 3 2 Unit description 21 3 3 Cooling cycle descrip...

Page 3: ...applied to the unit 4 Figure 2 Description of the labels applied to the electric panel 6 Figure 3 Lifting instructions 11 Figure 4 Unit positioning 12 Figure 5 Condenser control scheme with cooling to...

Page 4: ...D EIMWC003H02 18_02EN 4 34 Figure 1 Description of the labels applied to the unit Single circuit unit...

Page 5: ...R solenoid valve circ 1 1 8 VR 5 Evaporator entering water temperature sensor 17 High pressure switch 6 Air purge 18 Discharge temperature sensor 7 Water drain 19 Oil Pressure Transducer 8 Liquid line...

Page 6: ...unit Identification of labels 1 Manufacturer s logo 8 Lifting instructions 2 Electricity warning 9 Refrigerant 3 Shutoff valve position 10 W012 Symbol 4 Wire tightness check 11 Attention Closed Valve...

Page 7: ...e refrigerant leaks 13 disable the unit from the mains using the main switch before opening the control panel 14 check that the unit has been grounded correctly before starting it 15 install the machi...

Page 8: ...e screw compressor and adjustment inverters are designed and constructed to cool and or heat buildings or industrial processes Daikin technicians specifically trained for this purpose must start the f...

Page 9: ...azing or similar activity and then only provided the refrigerant concentration is monitored and adequate ventilation is ensured Such open flames shall not be left unattended A remote switching emergen...

Page 10: ...0 303 kg m3 0 07575 kg m3 16500 ppm All electrical equipment not only the refrigerating system shall be selected to be suitable for use in the zones identified in the risk assessment Electrical equipm...

Page 11: ...n pads optional are shipped separately Make sure these items if required are delivered with the unit Use extreme caution when handling the unit to prevent damage to the control panel and the refrigera...

Page 12: ...prevent refrigerant accumulation inside that can deprive air of the right oxygen content that can cause asphyxiation In this regard we recommend the application of harmonized standard EN378 3 Safety a...

Page 13: ...freezing The flow switch must not be used as a machine control system The absence of the flow switch on the evaporator water connection voids the warranty for frost damage The evaporator and condenser...

Page 14: ...f untreated water can result in corrosion erosion mud fouling and formation of algae Daikin Applied Europe is not liable for equipment damage or malfunction due to a lack of a water treatment or water...

Page 15: ...and high condenser inlet water temperature may be inhibited Glycol must be used for all applications with the evaporator outlet fluid below 4 C The maximum permissible water temperature in the evapor...

Page 16: ...C Ref 2c standard unit opt 174 Low Brine Limit for Propylene Glycol ELWT 8 C Ref 3 standard unit opt 111 High temperatures kit Ref 4a standard unit opt 08 Brine opt 111 high temperature kit Limit for...

Page 17: ...5 lt kW Process 6 6 lt kW 5 0 lt kW Variable capacity 6 6 lt kW 5 0 lt kW Calculation example Cooling capacity at 100 670 kW Minimum system volume for conditioning 670 x 3 3 2211 lt Minimum system vol...

Page 18: ...re should not be less than 20 C at full water tower flow rate If the water temperature must be lower even the water flow must be reduced proportionately To modulate the water flow to the condenser ins...

Page 19: ...onsible for connecting the safety valve to the purge pipe and pipe dimensioning In this regard refer to the harmonized standard EN13136 to dimension the drain pipes to be connected to the safety valve...

Page 20: ...tor becomes familiar with the equipment before operating the machine In addition to reading this manual the operator should study the operation manual and the wiring diagram supplied with the unit to...

Page 21: ...ased to the condensation water which heats accordingly The condensed fluid at saturation temperature passes through the sub cooling section where it yields heat to further increase cycle efficiency Th...

Page 22: ...control protects the compressor from any operating faults The oil filter must be replaced within the first 500 hours of compressor operations The electronic controller generates an alarm for high oil...

Page 23: ...te that all units are also provided with the Control Manual Figure 7 Unit interface 3 3 8 Safeties for each refrigerant circuit High pressure pressure switch Motor cooling High compressor delivery tem...

Page 24: ...thermistors the controller is able to constantly monitor winding temperature and stop the corresponding compressor in the event that the temperature exceeds the safety value Repeated interventions of...

Page 25: ...tem the heat transfer fluid should be checked for the possible presence of refrigerant After any repair work the safety devices for example refrigerant detectors and mechanical ventilation systems sho...

Page 26: ...f compressors installed on the machine The valves are managed and controlled by the main electronic controller that optimizes the flow of refrigerant gas to the evaporator according to machine operati...

Page 27: ...Typical single circuit cooling circuit Fig 7 Typical dual circuit cooling circuit Legend 1 Compressor 15 Oil injection valve 2 Delivery valve optional 16 Oil injection solenoid valve 3 Oil Condenser S...

Page 28: ...0 5 and 4 C d The difference between condensing temperature and condenser outlet water temperature is between 1 and 3 C 5 Make sure the indicator on the liquid tube is full If one of these parameters...

Page 29: ...ed Europe Spa cannot be held liable for damage caused by untreated or improperly treated water 4 5 2 Seasonal start up Annual start up is a good time to assess motor winding ground resistance A semi a...

Page 30: ...ntative technical staff a Oil Analysis have to be performed each year or every 5000 hours of operation whichever shall first occur b Change the oil filter if p 2 bar c Check water temperature entering...

Page 31: ...operable Water system operated and flow balanced to meet unit design requirements Electrical Power leads connected to unit main terminal block Power leads have been checked for proper electrical phasi...

Page 32: ...g instructions Any refrigerant charge for each circuit 1 2 3 added during commissioning the total refrigerant charge 1 2 3 calculate the greenhouse gas emission with the following formula 1000 Use the...

Page 33: ...rdance with local laws regarding disposal and if in scope with the national laws implementing the Directive 2012 19 EU RAEE Batteries and electrical components must be sent to specific waste collectio...

Page 34: ...contained herein are liable to change without notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A cannot be held liable for direct or indirect damage in the bro...

Reviews: