MCAC-ATSM-2017-08 Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz)
53
200kW module (KEM-200 HN3)
No
Code
Trouble
1
E0
Error of outdoor EEPROM
2
E1
Power phase sequence error
3
E2
Communication error
4
E3
Total water outlet temperature sensor error (Be valid for main unit)
5
E4
Unit outlet water temperature sensor error
6
E5
Pipe temperature sensor error in condenser A
7
E6
Pipe temperature sensor error in condenser B
8
E7
Outdoor ambient temperature sensor error
9
E8
Output of the power protector error
10
E9
Water flow detection error(Manual recovery)
11
EA
(Reserved failure code)
12
Eb
Anti-freezing
temperature sensor error in shell and tube exchanger
13
EC
Wired controller detected that the units on-line have decreased.
14
Ed
(Reserved failure code)
15
EF
Inlet water temperature sensor error
16
P0
High pressure or air discharge temperature protection in system A(Manual recovery)
17
P1
Low pressure protection in system A(Manual recovery)
18
P2
High pressure or air discharge temperature protection in system B(Manual recovery)
19
P3
Low pressure protection in system B(Manual recovery)
20
P4
Current protection in system A(Manual recovery)
21
P5
Current protection in system B(Manual recovery)
22
P6
Condenser high pressure protection in system A
23
P7
Condenser high pressure protection in system B
24
P8
(Reserved failure code)
25
P9
Outlet and inlet water temperature difference protection
26
PA
Low ambient temperature drive-up protection
27
Pb
System
anti-freezing
protection
28
Pc
Anti-freezing pressure protection in system A(Manual recovery)
29
Pd
Anti-freezing pressure protection in system B(Manual recovery)
30
PE
Low-temperature protection of evaporator(Manual recovery)
Summary of Contents for KEM-30 DNH3
Page 2: ......
Page 5: ...2 1 2 External appearance KEM 130 HN3 KEM 200 HN3 KEM 250 HN3 KEM 30 DHN3 KEM 65 DHN3 ...
Page 33: ...30 130kW module ...
Page 35: ...32 250kW module ...
Page 39: ...36 200kW module ...
Page 73: ...130kW module 200kW module Input of airflow Input of airflow Input of airflow Input of airflow ...
Page 159: ......
Page 160: ......