14.6.8 K01-BACNET KEM alarm, protective status object list
This device provides 16 alarm objects and 6 K01-BACNET KEM objects with general device status for the
wired controller; to be used for the building management system supported K01-BACNET KEM agreement
or other systems.
And K01-BACNET KEM alarm, protective status object list are corresponding to the list in WEB, in web, yes
means there has error or under protective status, no means system operate normally, in K01-BACNET KEM
system, active means this object has error or under protective status.
Error list
Protection list
BI1
BI15
BI
BI2
BI3
BI4
BI6
BI7
BI8
BI9
BI10
BI11
BI12
BI13
BI14
BI5
BI16
No.
1
KJR120A/MBTE
Code
E0
Error of outdoor EEPROM
2
3
4
E1
Power phase sequence error
E2
Pipe temperature sensor error in condenser A
Communication error
Error of total outlet water.temp sensor(Be valid for main unit)
Pipe temperature sensor error in condenser B
Outdoor ambient temperature sensor error
Output of the power protector error
Water flow detection error(manual recovery)
(Reserved failure code)
Anti-freezing temperature sensor error in shell and tube exchanger
E3
E4
E5
E6
E7
E8
E9
EA
EB
EC
ED
EE
EF
Error of unit outlet water.temp sensor
Wired controllor detected that the units on-line have
decreased.
Error of inlet water temperature sensor
5
6
7
16
15
14
13
12
11
10
9
8
Continuous 3 times PE protection in 1 hou
r, need to
re-power on(theold main control panel)
EEPROM error of wired controller
Summary of Contents for KEM-30 DNH3
Page 2: ......
Page 5: ...2 1 2 External appearance KEM 130 HN3 KEM 200 HN3 KEM 250 HN3 KEM 30 DHN3 KEM 65 DHN3 ...
Page 33: ...30 130kW module ...
Page 35: ...32 250kW module ...
Page 39: ...36 200kW module ...
Page 73: ...130kW module 200kW module Input of airflow Input of airflow Input of airflow Input of airflow ...
Page 159: ......
Page 160: ......