MCAC-ATSM-2017-08 Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz)
47
Heating:
Hot water outlet
temp.
Ambient temp.(
)
-10
-6
-2
2
7
10
13
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(
)
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
40.00
124.31
38.17
155.39
43.37
182.81
48.19
203.13
52.38
220.79
55.14
247.28
58.45
284.38
63.12
41.00
120.14
38.95
150.36
44.26
177.10
49.18
197.00
53.45
214.36
56.26
239.65
59.64
275.12
64.41
42.00
116.66
39.74
146.19
45.16
172.40
50.18
191.98
54.54
209.13
57.41
233.39
60.86
267.46
65.73
43.00
113.85
40.55
142.84
46.08
168.65
51.20
188.01
55.66
205.03
58.58
228.40
62.10
261.29
67.07
44.00
111.64
41.38
140.26
47.02
165.79
52.25
185.03
56.79
202.00
59.78
224.62
63.37
256.52
68.44
45.00
110.03
42.22
138.40
47.98
163.79
53.31
183.00
57.95
200.00
61.00
222.00
64.66
253.08
69.83
46.00
107.87
42.65
135.86
48.46
160.97
53.85
180.06
58.53
197.00
61.61
218.28
65.31
248.40
70.53
47.00
104.69
43.50
132.01
49.43
156.60
54.92
175.36
59.70
192.08
61.81
212.43
66.61
241.33
71.94
48.00
100.55
44.80
126.96
50.91
150.78
56.57
169.04
61.49
185.35
63.67
204.63
68.61
232.05
74.10
49.00
95.08
46.60
120.20
52.95
142.93
58.83
160.41
63.95
176.08
66.21
194.05
71.36
219.66
77.06
50.00
88.96
48.93
112.61
55.60
134.05
61.78
150.62
67.15
165.52
69.52
182.07
74.92
205.74
80.92
Note:
The inlet/outlet water temperature difference is 5
.
Summary of Contents for KEM-30 DNH3
Page 2: ......
Page 5: ...2 1 2 External appearance KEM 130 HN3 KEM 200 HN3 KEM 250 HN3 KEM 30 DHN3 KEM 65 DHN3 ...
Page 33: ...30 130kW module ...
Page 35: ...32 250kW module ...
Page 39: ...36 200kW module ...
Page 73: ...130kW module 200kW module Input of airflow Input of airflow Input of airflow Input of airflow ...
Page 159: ......
Page 160: ......