10.3 Typical malfunction solutions
1) High pressure and discharged temperature protection
Yes
No
No
Yes
Yes
Yes
Yes
Yes
High pressure and
discharged
protection.
No
No
Yes
Yes
Yes
Yes
No
No
No
No
High
pressure
protection.
Blower stops rotating or rotates in
reversed direction in cooling mode,
water pump is not open or the flow.
Couldn’t start the EXV.
Pressure controller is broken
or the joint is loose.
Fin heat exchanger in cooling mode is
too dirty or aged, or too heavy
encrustation in shell and tube for heating.
EXV, capillary and filter are
dirty, blocking.
Discharge
temperature
protection.
See the analysis of
discharge temp. protection
malfunction.
Inspect fan motor and
capacitor (1phase) or
start up the water pump.
Replace EXV or coil.
Replace press controller,
fixed joint.
Clean heat exchanger.
Replace EXV, capillary
and filter.
There is air and filled refrigerant
too much in system (Generally
occur after maintenance.)
PCB mistakes to alarm.
Empty, vacuuming and
append refrigerant if
necessary.
Check if it happened
frequently, if yes, please
replace PCB.
Inform
the
customer
service center.
Summary of Contents for KEM-30 DNH3
Page 2: ......
Page 5: ...2 1 2 External appearance KEM 130 HN3 KEM 200 HN3 KEM 250 HN3 KEM 30 DHN3 KEM 65 DHN3 ...
Page 33: ...30 130kW module ...
Page 35: ...32 250kW module ...
Page 39: ...36 200kW module ...
Page 73: ...130kW module 200kW module Input of airflow Input of airflow Input of airflow Input of airflow ...
Page 159: ......
Page 160: ......