Connections
Type
400V, 3-phase
230V, 3-phase
115V, 2-phase
Power sockets
Number
16 A; 230V / 1~ / N / PE
3
–
–
16 A; 400V / 3~ / N / PE
1
–
–
16 A; 230V / 2~ / PE
–
2
–
32 A; 230V / 3~ / PE
–
1
–
16 A; 230V /3~ / PE
–
1
–
32 A; 115V / 2~ / PE
–
–
1
16 A; 115V / 2~ / PE
–
–
2
Tab. 49 Connection sockets
Circuit breaker
Type
400V, 3-phase
230V, 3-phase
115V, 2-phase
Safety cut-out [A]
Number:
16
1
1
2
32
–
1
1
Tab. 50 Circuit breaker
Operating limits
(to EN 60034-22, page 10, table)
Characteristics
Value
Design category
G3
Voltage adjustment range [%]
±5
Static voltage deviation [%]
1
Maximum dynamic voltage drop [%]
−15
Maximum dynamic voltage rise [%]
20
Maximum voltage settling time [ms]
1500
Maximum voltage asymmetry [%]
1
Tab. 51 Generator operating limits
Maximum power loading by consumers
Resistive consumers include lamps and heaters, for example.
Electric motors and transformers are inductive consumers.
Nominal rating conditions
■ Ambient temperature: 77 °F
■ Max. height above sea level of the place of installation: 3000 ft
2
Technical Data
2.9
Options
20
Operator Manual Portable Rotary Screw Compressor
MOBILAIR M82 SIGMA CONTROL SMART
No.: 901783 08 USE