Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] / 65534 [%
Slim / min] / 1
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
P(f) settling time
200 – 2,000 [ms] /
200 [ms] / 1 [ms]
Password protection
Status
1. Set the P(f) settling time mode.
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Voltage-dependent
NOTE: Activate voltage-dependent power reduction in the
P(U) menu.
4
1
2
3
4
Operation mode
OFF | ON
F
Regelverfahren aktivieren.
Off
: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
4
1
2
3
4
Reference power
Actual power |
Nominal power
F
Select the power-dependent control method.
4
1
2
3
4
Bewertete Spannung
Maximum phase
voltage | Positive se-
quence voltage
F
Select the voltage to be rated.
Defines which voltage in a three-phase system is to be evaluated.
4
1
2
3
4
Hysteresis mode
Off | On
NOTE: Hysteresis mode affects the shutdown response of
P(U).
F
Activate the mode.
4
1
2
3
4
Deactivation gradient
0 – 65,534 [% /
min] / 100 [% /
min] / 1
F
Set the gradients for the power limitation.
4
1
2
3
4
Deactivation time
0 – 60000000 [ms] /
0 [ms] / 1000 [ms]
F
Specify the time for voltage reduction.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] / 65534 [%
Slim / min] / 1
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Settling time
500 – 120000 [ms] /
2000 [ms] / 10
[ms]
F
Specify the settling time.
Manual
Configuration and operation | 9
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S