Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Node 1- Node 10
0-100% [ % Slim] /
0 , 50 , 100 % [ %
Slim] / 1
F
Power factor for 1st ,10th ... node as a percentage of the maximum
power.
NOTE: For the 1st node, the power must be 0%; for the last
node, the power must be 100%. The power values of the
nodes must increase continuously.
0,3 – 1 [ind/cap] /
1 / 0.001
F
Specify the cos ϕ of the node.
Übererregt | Un-
tererregt
Password protection
Status
F
If a reactive power not equal to 1 is selected: Select the type of
phase shift.
NOTE: Over-excited relates to a capacitive load, under-excited
relates to an inductive load.
1. Activate optional password protection.
2. Confirm the action field.
4
1
2
3
4
Q(U)
NOTE: Define Q(U).
4
1
2
3
4
Lock-In power
0 – 100 [% Slim] /
100 [% Slim] / 1
F
Set the active power as % of rated power above which control is ac-
tivated.
4
1
2
3
4
Lock-Out power
0-20 [% Slim] / 5
[%Slim] / 1
F
Set the active power as % of rated power below which control is de-
activated.
4
1
2
3
4
Lock-In time
0 – 60,000 [ms] /
30,000 [ms] / 1,000
[ms]
Lock-Out time
0 – 60,000 [ms] /
30,000 [ms] / 1,000
[ms]
F
Set the length of time that the active power must remain above the
lock-in / lock-out power level before control is activated.
4
1
2
3
4
Dead time
0 -10,000 [ms] / 0
[ms] / 1
F
Set the intentional delay for the start of the Q(U) function.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] / 65534 [%
Slim / min] / 1
1. Maximum change in the reactive power in the event of a change to
over-excited mode.
2. Maximum change in the reactive power in the event of a change to
under-excited mode.
4
1
2
3
4
Settling time
1,000 – 120,000
[ms] / 1,000 [ms]
10
F
Set the response speed of the control.
4
1
2
3
4
Minimum cos-phi Q1
- Minimum cos-phi Q4
0 – 1 / 0 /
0.001
F
Enter the minimum cos ϕ factor for quadrants 1 and 4.
9 | Configuration and operation