![Kaco blueplanet gridsave 110 TL3-S Manual Download Page 69](http://html1.mh-extra.com/html/kaco/blueplanet-gridsave-110-tl3-s/blueplanet-gridsave-110-tl3-s_manual_649205069.webp)
Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
Power gradient in-
creasing & power gra-
dient decreasing
1 – 65,534 [% S
lim
/
min] / 65,534 [% S
lim
/
min] / 1
Maximum change in the reactive power %S
lim
/min in the event of a
change to over-excited mode
NOTE: The gradient is overlaid with the settling time.
Settling time
1,000 – 120,000
[ms] / 5,000 [ms]
10
Determines the dynamic behaviour in the event of a change in the cos ϕ
set value. With a change of the active power or the lock-in and lock out
voltage, the cos ϕ is changed according to a PT-1 characteristic curve
with a settling time of 5 Tau.
Number of nodes
2 – 10
Specify the number of nodes for the cos ϕ/(p/pn) characteristic curve
1. Stützstelle … 10.
Stützstelle
0V - Max. voltage in
continuous operation
Power of the node as a percentage of the maximum power.
For the 1st node, the power must be 0%; for the last node, the power
must be 100%. The power values of the nodes must increase continu-
ously.
Note: Storage inverters only for feed-in operation
1 – 0,3 / 1 /
0.001
Reactive power of the node as a percentage of the maximum power
Over-excited | un-
der-excited
Reactive power mode Under-excited relates to inductive load, over-ex-
cited relates to capacitive load.
Q(U) 10 nodes
Lock-in power
0 – 100 [% S
lim
] /
20 [% S
lim
] / 1
Power threshold, function is activated if limit value is exceeded.
Lock-out power
0 – 100 [% S
n
] / 5
[% S
n
] / 1
Power threshold, function is activated if limit value is undershot.
Lock-In time
0 – 60,000 [ms] /
30,000 [ms] / 1,000
[ms]
Length of time that the active power must remain below the lock-in
power level before control is deactivated.
Lock-Out time
0 – 60,000 [ms] /
30,000 [ms] / 1,000
[ms]
Length of time that the active power must remain below the lock-out
power level before control is deactivated.
4
1
2
3
4
Downtime
0 -10,000 [ms] / 0
[ms] / 1
If the voltage switches from a characteristic curve section with Q=0 to a
characteristic curve section with Q≠0 under active control, then the re-
active power setting process is delayed by the set dead time. Once the
dead time has expired, the control circuit is no longer subject to a delay
and the set transient time determines the transient behaviour.
Rise Outg. grad. & Fall.
Outg. grad.
increasing | decreas-
ing
In addition to configuring the dynamic behaviour using the transient
time corresponding to a first-order filter, the reactive power setting can
be determined by a maximum gradient - this means the maximum
change in the reactive power per time period.
1 – 65,534 [% S
lim
/
min] / 65,534 [% S
lim
/
min] / 1
Maximum change in the reactive power %S
lim
/min in the event of a
change to over-excited mode
NOTE: The gradient is overlaid with the settling time.
Manual
Specifications | 10
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 69
EN-US