Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Frequency
NOTE: Opportunity to monitor frequency trip-off
4
1
2
3
4
Trip underfrequency
monitoring
Status
F
Activate if necessary.
4
1
2
3
4
Number of trip under-
frequency levels
1- 5 / 2 / 1
F
Specify the number of support levels.
4
1
2
3
4
Trip underfrequency
level 1
45 – 65 [Hz] / 47.5
[Hz] / 0.01
Trip underfrequency
time level 1
0– 1000000 [ms] /
100 / 1
NOTE: If the grid frequency is within the deactivation range
for the duration of the deactivation time, then the function is
deactivated.
F
Define range and trip-off time.
4
1
2
3
4
Trip underfrequency
level 2 - 5
42.5 – 65 [Hz] /
47.5 [Hz] / 0.01
Trip underfrequency
time level 2 – 5
0– 1000000 [ms] /
100 / 1
4
1
2
3
4
Trip overfrequency
monitoring
Status
F
Activate if necessary.
4
1
2
3
4
Number of trip overfre-
quency levels
1- 5/ 2 / 1
F
Specify the number of support levels.
4
1
2
3
4
Trip overfrequency
level 1
45.0– 65 [Hz] /
51.5 [Hz] / 0.01
Trip overfrequency
time level 1
0 – 10000000 [ms] /
100 / 1
NOTE: If the grid frequency is within the deactivation range
for the duration of the deactivation time, then the function is
deactivated.
1. Define range and trip-off time.
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Trip overfrequency
level 2 – 5
45,0– 67.5 [Hz] /
51.5 [Hz] / 0.01
Trip overfrequency
time level 2 – 5
0 – 10000000 [ms] /
100 / 1
Password protection
Status
9 | Configuration and operation
Manual
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 48
EN-US