Step: Network parameters
↻
The country and grid type have been selected.
.
NOTE: By default, IP addresses are assigned via the plant DHCP
server.
.
NOTE: If static IP addresses are required, you will have to assign
these.
.
CAUTION! In this case, it is no longer possible to distribute the con-
figuration via the Segment Controller as this would then be part of
the configuration and ultimately all inverters in the same segment
would be assigned the same IP address.
1. Activate
DHCP
or enter the
IP address
at the deactivated DHCP.
2. Confirm the action field.
ð
Pressing the
Next
button will take you to the next installation step.
Fig. 38:
Menu item: [See sec-
Step: Localization
↻
The network parameters have been set up.
1. Set the
date
,
time and time zone
or arrange for synchronization with
the client.
2.
NOTE: An NTP server needs to be activated for synchronization purposes
7
3. Select temperature unit from the dropdown menu.
4. Confirm the action field.
ð
Pressing the
Next
button will take you to the next installation step.
Fig. 39:
Menu item: [See sec-
Step: Cloud & portal configuration
↻
Localization has been carried out.
1. If available, activate
Web portal
and select
Portal
from the dropdown
menu.
2. Configure the portal.
3. Confirm the action field.
ð
Pressing the
Next
button will take you to the next installation step.
Fig. 40:
Menu item: [See sec-
Step: ModBus
↻
Portal configuration completed.
.
NOTE: The device supports MODBUS/TCP and conventional SUNSPEC
models. If there are concerns over security, write access can be deac-
tivated.
1. Specify the
Modbus port
and determine
Read/write access
.
2. Confirm the action field.
ð
Pressing the
Next
button will take you to the next installation step.
Fig. 41:
Menu item: [See sec-
7
It is preferable to install this on a plant component. It is also possible to select an NTP server localized on the
internet provided the device has direct access to the internet.
9 | Configuration and operation
Manual
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 36