4
1
2
3
4
Minimum operating
voltage
45 – 125.0 [% Unom]
&
Maximum operating
voltage
45 – xxx [% Unom]
Password protection
Status
F
Set voltage range for the active control process.
4
1
2
3
4
Zero current under-
voltage threshold
Zero current threshold
over voltage
0 – 184 V / 253 – 340
V
F
Set the voltage threshold for zero current mode.
4
1
2
3
4
Reactive current limita-
tion
0 – 100 % [ % Imax]
F
Set the reactive power limitation.
4
1
2
3
4
Minimum support time
1000 – 15000 ms
F
Set the minimum support time.
4
1
2
3
4
Connection cond.
NOTE: The device checks the grid voltage and grid frequency.
The grid feed-in mode begins if the measurements are within
the set ranges.
F
Set minimum and maximum values for connection.
4
1
2
3
4
Min. conn. voltage
after grid failure
Max conn. voltage
after grid failure
F
Set min. and max. switch-on voltage after grid monitoring.
4
1
2
3
4
Min. conn. frequency
after grid failure
Max. conn. frequency
after grid failure
F
Set min. and max. switch-on frequency after grid monitoring.
4
1
2
3
4
Monitoring time PV
voltage
F
Set time for voltage monitoring.
Monitoring time grid
voltage
F
Set time for voltage monitoring.
4
1
2
3
4
Waiting time after grid
failure
F
Set wait time for grid monitoring.
4
1
2
3
4
Enhanced Island Detec-
tion
NOTE: Grid operators require shutdown of the device with
standalone grid detection. More detailed information at:
4
1
2
3
4
Frequency shift
Off | On
F
Activate frequency shift.
Manual
Configuration and operation | 9
KACO blueplanet 3.0 TL3 KACO blueplanet 4.0 TL3 KACO blueplanet 5.0 TL3 KACO blueplanet 6.5 TL3 KACO
blueplanet 7.5 TL3 KACO blueplanet 8.6 TL3 KACO blueplanet 9.0 TL3 KACO blueplanet 10.0 TL3
Page 47
EN