Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Min. cos-phi Q1 - Min.
cos-phi Q4
NOTE: In the event of a significant voltage deviation, the max-
imum reactive power adjustment range can be limited by a
minimum cos φ in order to prevent an excessive reactive
power supply and, as a result, a significant reduction in the
maximum active power that can be fed in.
F
Enter the minimum cos ϕ factor for quadrants 1 and 4.
4
1
2
3
4
Priority mode
Q priority | P priority
F
Set priority for reactive power – Q or active power – P.
NOTE: When it comes to P priority, the reactive power adjust-
ment range is limited subject to the active power that is cur-
rently available and fed in.
4
1
2
3
4
Active curve
1 - 4
F
Select active curve.
NOTE: Up to 4 characteristic curves can be configured inde-
pendently and one of them can be activated for regulation
each time.
4
1
2
3
4
Reset the curve
F
Reset active curve to the default setting.
4
1
2
3
4
Number of nodes
2 - 10
NOTE: The maximum number of configurable nodes depends
on the selected grid type.
F
Specify the number of nodes for the Q(U) characteristic curve.
4
1
2
3
4
Exten. standalone grid
NOTE: Grid operators require shutdown of the device with
standalone grid detection.
F
Further parameterisation is possible via the web interface.
BE CH-NS
CY DE-NS
DK JP-50HZ
JP-60HZ
LU-NS TW
UD
4
1
2
3
4
Grid errors
NOTE: Display of grid faults.
F
To show the last 5 grid fault messages, press the
Show button.
4
1
2
3
4
Advanced features
F
Further parameterisation is possible via the web interface
4
1
2
3
Information
Open the menu: Press Right arrow button or Enter button.
4
1
2
3
4
Inverter type
Displays the type designation of the device. If feed-in power is actively
limited: display maximum power in kW.
4
1
2
3
4
Display country
Displays the selected country setting. Optional: Displays the grid type if
a grid type has been selected.
4
1
2
3
4
Vendor
The display shows information about the device manufacturer.
9.4.2
Configuration via web user interface
NOTE
In addition to the parameters in the chapter [See section 9.4.1
Page 35], additional parameters are available
and accessible via the web user interface. To do so, enable
Remote config
in
Network
under
Web-
server
and enter the device IP address into your browser.
4
1
2
3
4
Operating settings
NOTE: Options for advanced setting of the operating paramet-
ers.
4
1
2
3
4
DC starting volt.
The device begins feed-in as soon as this DC voltage is present.
F
Set the starting voltage.
Manual
Configuration and operation | 9
KACO blueplanet 3.0 TL3 KACO blueplanet 4.0 TL3 KACO blueplanet 5.0 TL3 KACO blueplanet 6.5 TL3 KACO