4
Technical data
4.1
Electrical data
3.0 TL3
4.0 TL3
5.0 TL3
6.5 TL3
7.5 TL3
8.6 TL3
9.0 TL3
10.0 TL3
DC Input levels
Maximum recommended PV
generator power
3.6 kW
4.8 kW
6 kW
7.8 kW
9 kW
10.3 kW
10.8 kW
12 kW
MPPrange@Pnom
200 - 800 V
240-800 V 310-800 V 350-800 V 403-800 V 420-800 V 470-800 V
Working range
200 V -950 V
Rated voltage
653 V
Starting voltage
250 V
Open circuit voltage
1,000 V
Max. input current
2
2 x 11 A
Number of strings
1
Number of MPP controls
2
Max. short-circuit current (ISC
max.)
2 x 16 A
Input source feedback current
0 A
Polarity safeguard
yes
String fuse
no
DC overvoltage protection
Built-in
3.0 TL3
4.0 TL3
5.0 TL3
6.5 TL3
7.5 TL3
8.6 TL3
9.0 TL3
10.0 TL3
AC Output levels
Nominal power
3 kVA
4 kVA
5 kVA
6.5 kVA
7.5 kVA
8.6 kVA
9 kVA
10 kVA
Rated voltage
220 / 380 V [3/N/PE];
230 / 400 V [3/N/PE];
240 / 415 V [3/N/PE]
Voltage range: continuous op-
eration
305 V - 480 V [Ph-Ph]
Rated current
3x 4.20 A
[@415V];
3x 4.35 A
[@400V];
3x 4.60 A
[@380V]
3x 5.60 A
[@415V];
3x 5.80 A
[@400V];
3x 6.10 A
[@380V]
3x 7.00 A
[@415V];
3x 7.25 A
[@400V];
3x 7.60 A
[@380V]
3x 9.10 A
[@415V];
3x 9.50 A
[@400V];
3x 9.90 A
[@380V]
3x 10.50
A
[@415V];
3x 10.90
A
[@400V];
3x 11.40
A
[@380V]
3x 12.00
A
[@415V];
3x 12.50
A
[@400V];
3x 13.10
A
[@380V]
3 x 12.60
A
[@415V];
3 x 13.00
A
[@400V];
3 x 13.70
A
[@380V]
3x 14.95
A
[@415V];
3x 14.50
A
[@400V];
3x 15.20
A
[@380V]
Max. continuous current
3 x 4.8 A
3 x 6.4 A
3 x 8.0 A 3 x 10.5 A 3 x 12.0 A 3 x 13.2 A 3 x 14.0 A 3 x 15.5 A
Contribution to peak short-cir-
cuit current ip
34.96 A
35 A
41 A
35 A
41 A
2
The "Max. input current" is the maximal theoretical value for operation with full power when the feed-in
power is low. The device is limited to the maximum AC power.
The "Max. short-circuit current (ISC
max
.)" defines together with open circuit voltage (U
DCmax
) the characteristic of
the connected PV generator. This is the relevant value for string sizing and is the absolute maximal limit for in-
verter protection. The connected PV-Generator must be designed, that the max short circuit current is below
or equal to the ISC
max
of the inverter under all foreseeable conditions and therefore complies with IEC 61730
Class A. In no condition the design may result in a greater short circuit current than ISC
max
4 | Technical data
Manual
KACO blueplanet 3.0 TL3 KACO blueplanet 4.0 TL3 KACO blueplanet 5.0 TL3 KACO blueplanet 6.5 TL3 KACO
blueplanet 7.5 TL3 KACO blueplanet 8.6 TL3 KACO blueplanet 9.0 TL3 KACO blueplanet 10.0 TL3
Page 12
EN