EPC (extended power
control)
NOTE: EPC settings
Fallback Power
0 – 100 %
1. Set fallback power.
2. Set time until shutdown takes place.
4
1
2
3
4
PC (power control)
NOTE: The PowerControl function monitors compliance with
the specifications set above for cos-phi, Q and P.
Fallback time
0 – 65535 s
1. Set fallback time for external power specification.
2. Transfer values with Apply button.
NOTE: After the set fallback time, external (RS485 or Modbus)
specifications for cos-phi, Q and P are reset to the respective
set fallback value (cos-phi constant, Q-con-stant or fallback
power).
.
NOTE: If the fallback time is set to 0s, external settings for
cos-phi, Q and P are not reset (operation continues with the
last received setpoint).
4
1
2
3
4
Power rampup active
NOTE: Power ramp-up is used to ramp up the power gradu-
ally. More detailed information at:
4
1
2
3
4
Power rampup gradi-
ent
1 – 600 [% / min]
F
Set increase.
4
1
2
3
4
Rampup on every con-
nect
Status
Rampup on first con-
nect
Status
Rampup after grid fail-
ure
Status
Password Protection
Status
1. Activate option.
2. Activate optional password protection.
3. Confirm action field
4
1
2
3
4
Priority mode
Q-Priority | P-Prior-
ity
F
Set priority for reactive power – Q or active power – P.
NOTE: When it comes to P priority, the reactive power adjust-
ment range is limited subject to the active power that is cur-
rently available and fed in.
4
1
2
3
4
Activation threshold
with overfrequency
50.2 – 70 (Hz)
Activation threshold
with underfrequency
40 – 45 (Hz)
1. Set frequency thresholds for activating the power limitation with
overvoltage.
2. Set the frequency thresholds for activating the power limitation
with undervoltage.
4
1
2
3
4
Power reduction P(U)
NOTE: To prevent the device from shutting down due to over-
voltage protection, the active power can be regulated in addi-
tion to reactive power control in order to reduce the active
power feed-in whereby the output voltage is reduced.
4
1
2
3
4
P(U) operation mode
Off | On
F
Activate the control process.
Off
: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
Manual
Configuration and operation | 9