Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
P(f) minimum deactiva-
tion frequency
45 – 61.5 [Hz] /
0.01 &
P(f) maximum deacti-
vation frequency
45 – 70 [Hz] / 0.01
F
Specify the minimum deactivation frequency in Hz.
NOTE: Only evaluated in mode 1.
The function is disabled if the frequency returns to the range between
the minimum and maximum deactivation threshold and remains within
this range for the duration of the deactivation time.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] / 65534 [%
Slim / min] / 1
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
P(f) settling time
200 – 2,000 [ms] /
200 [ms] / 1 [ms]
Password protection
Status
1. Set the P(f) settling time mode.
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Voltage-dependent
NOTE: Activate voltage-dependent power reduction in the
P(U) menu.
4
1
2
3
4
Operation mode
OFF | ON
F
Regelverfahren aktivieren.
Off
: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
4
1
2
3
4
Reference power
Actual power |
Nominal power
F
Select the power-dependent control method.
4
1
2
3
4
Bewertete Spannung
Maximum phase
voltage | Positive se-
quence voltage
F
Select the voltage to be rated.
Defines which voltage in a three-phase system is to be evaluated.
4
1
2
3
4
Hysteresis mode
Off | On
NOTE: Hysteresis mode affects the shutdown response of
P(U).
F
Activate the mode.
4
1
2
3
4
Deactivation gradient
0 – 65,534 [% /
min] / 100 [% /
min] / 1
F
Set the gradients for the power limitation.
4
1
2
3
4
Deactivation time
0 – 60000000 [ms] /
0 [ms] / 1000 [ms]
F
Specify the time for voltage reduction.
9 | Configuration and operation
Manual
KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
Page 64
EN-US