Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Dynamic reactive cur-
rent only
Off | On
NOTE: With FRT mode activated, the pre-fault reactive current
can be added.
F
If necessary, activate pre-fault reactive current.
4
1
2
3
4
Dead band mode
Mode 1 | Mode 2
F
Select dead band mode for the active control process.
4
1
2
3
4
Reference voltage
80.0 – 110.0 [%
Unom] 100 0.1
F
Set reference voltage for the active control process.
4
1
2
3
4
Minimum operating
voltage
45.0 – 125.0 [%
Unom] 0.1 &
Maximum operating
voltage
45.0 – 125.0 [%
Unom] 0.1
Password protection
Status
F
Set voltage range for the active control process.
4
1
2
3
4
Zero current threshold
undervoltage
0 – 80 [%Unom]
0.1
Zero current threshold
overvoltage
110 – 141.8 [%
Unom] 0.1
F
Set voltage threshold for zero current mode.
If one or more phase/phase or phase/neutral conductor voltages move
below or above the configured threshold, the inverter changes to zero
current mode. The total current is regulated to virtually zero.
4
1
2
3
4
Reactive current limita-
tion
0 – 100 [% Imax] /
100 [% Imax] / 1
F
Set the reactive power limitation.
4
1
2
3
4
Minimum support time
1,000 – 15,000
[ms] / 5,000 [ms]
10
F
Set the minimum support time.
4
1
2
3
4
Enhanced Island Detec-
tion
NOTE: Grid operators require shutdown of the device with
standalone grid detection. More detailed information at:
4
1
2
3
4
ROCOF operation
mode passive Off |
On
F
Activate passive grid influence by application of a frequency.
ROCOF operation
mode active Off |
On
F
Activate active grid influence by application of a frequency.
4
1
2
3
4
Frequency shift
Off | On
F
Activate frequency shift.
Manual
Configuration and operation | 9
KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
Page 51