Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Pulse period repetition
time
40 – 6000 [ms] /
1000 [ms] / 1 [ms]
F
Define period for detection.
4
1
2
3
4
ROCOF threshold stage
1 value 0.1 – 6.0
[Hz / s] / 0.1
ROCOF threshold stage
2 value 0.1 – 6.0
[Hz / s] / 0.1
F
Define threshold for ROCOF.
ROCOF threshold stage
1 time 0.10 – 5.00
[ s] / 0.1
ROCOF threshold stage
2 time 0.10 – 5.00
[ s] / 0.1
F
Define time value for ROCOF.
4
1
2
3
4
ROCOF proportionality
factor
-5000 – 5000 [
0
/
00
/
Hz / s] / 1
Status
1. Define the proportionality factor.
2. Confirm the action field.
4
1
2
3
4
Ramp Rate Limitation
NOTE: Opportunity to limit power in the case of an increasing
and decreasing grid frequency.
Operation mode
Status
F
Select operation mode.
Increasing gradient &
Decreasing gradient
1 – 65534 [%/min] /
65534 / 1
Password protection
Status
F
Set gradient.
This percentage relates to the nominal frequency.
1. Activate optional password protection.
2. Confirm the action field.
9 | Configuration and operation
Manual
KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
Page 52
EN-US