Step: Optional parameters
↻
String collector monitoring has been set up.
.
NOTE: Using the plant ID, the device followed by its firmware version
can be detected automatically in the Cloud/portal and assigned to
the relevant plant.
1. Enter the device name used to reach the device in the network.
.
NOTE: The coordinates identify the device installation location.
2. Confirm the action field.
ð
Pressing the
Next
button will take you to the next installation step.
Fig. 54:
Menu item: Only on the in-
stallation wizard!
Step: Finalizing the installation
↻
Optional parameters have been set.
1. Device configuration completed successfully. Please click "Finalize" to put the
device into operation.
2. Specify a name for the device installation report.
3. Confirm the action field.
ð
The initial installation is now complete. Specify access for device(s).
Fig. 55:
Menu item: Only on the in-
stallation wizard!
9.2
Signal elements
The 3 LEDs on the device show the different operating states. The LEDs can display the following states:
LED illuminated
LED flashing
LED not illuminated
Operating status
LED
Icon
Description
Start
The green „
Operation
“ lights up when AC and DC voltage is
present.
If the LED flashes, the internal communication between the com-
ponents is established. After flashing, the device is ready to feed in
power.
If the LED continues to flash permanently, the internal communica-
tion is disturbed.
Feed-in start
The green LED „
Operation
“ lights.
The green LED „
Feed-in
“ lights up after the end of the country-
specific waiting time*.
The device feeds into the grid.
The interface switch engages audibly.
NOTE: Both LEDs also lights in "QonDemand"-operating
mode.
Feed-in mode with re-
duced power
The green LED „Operation“ lights.
The green LED „Feed-In“ flashes because one of the modes: inter-
nal power reduction, external power reduction, reactive power re-
quest or island operation is pending.
The device feeds into the grid.
The interface switch engages audibly.
Non-feed mode
The green LED „
Operation
“ lights.
Manual
Configuration and operation | 9
KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
Page 43