o
Switch on mains voltage.
i
The 1-10 V ballasts can be switched by briefly pressing the
Prog
button.
Status-LED (3) lights up: switched on
Status LED (3) off: switched off
o
Perform commissioning.
o
Mount the cover.
5.2 Commissioning
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
During commissioning, cover the parts carrying voltage on radio transmitters
and actuators and in their surrounding area.
i
The actuator can also be commissioned with eNet Server as an alternative to the
commissioning described here.
Connecting to radio transmitters
Load is switched off.
o
Press the
Prog
button for longer than 4 seconds.
The status LED (4) flashes after 3 seconds. The actuator is in programming mode for
approx. 1 minute.
o
Switch radio transmitter to programming mode (see radio transmitter instructions).
o
Trigger telegram on the radio transmitter.
The status LED lights up for 5 seconds.
The actuator is connected to the radio transmitter. The actuator and radio transmitter exit
the programming mode automatically.
i
If the status LED of the control unit flashes 3 times at 1-second intervals for
approx. 5 seconds, then the programming operation was not successful. All the memory
locations in the actuator or radio transmitter are occupied.
i
All On and All Off buttons of a radio transmitter are connected to the actuator automatically
as soon as the first connection to the radio transmitter takes place. Scene buttons must be
connected separately.
Disconnecting connection to a radio transmitter
o
Carry out the same steps as when connecting (see Connecting to radio transmitter).
The status LED (3) flashes quickly for 5 seconds. The actuator is disconnected from the
radio transmitter. The actuator and radio transmitter exit the programming mode
automatically.
i
If there several connections or scene buttons for a radio transmitter, all connections must
be disconnected individually.
i
All On and All Off buttons of a radio transmitter are disconnected automatically as soon as
the last connection to the radio transmitter is disconnected. Manual disconnection is not
possible.
Resetting actuator to default setting
All connections to radio transmitters are disconnected and parameters are reset to default
setting.
i
The connections in the radio transmitters are preserved and must be deleted separately.
Load is switched off.
o
Press the
Prog
button for at least 20 seconds.
The status LED flashes after 4 seconds. After 20 seconds the status LED flashes faster.
o
Release
Prog
button and press briefly once again within 10 seconds.
The status LED flashes more slowly for approx. 5 seconds.
4/12
82581023
J0082581023
29.03.2017
eNet radio push-button controller 1-10 V 1-gang mini