background image

o

Switch on mains voltage.

i

The 1-10 V ballasts can be switched by briefly pressing the 

Prog

 button.

Status-LED (3) lights up: switched on
Status LED (3) off: switched off

o

Perform commissioning.

o

Mount the cover.

5.2 Commissioning

DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
During commissioning, cover the parts carrying voltage on radio transmitters
and actuators and in their surrounding area.

i

The actuator can also be commissioned with eNet Server as an alternative to the
commissioning described here.

Connecting to radio transmitters 

Load is switched off.

o

Press the 

Prog

 button for longer than 4 seconds.

The status LED (4) flashes after 3 seconds. The actuator is in programming mode for
approx. 1 minute.

o

Switch radio transmitter to programming mode (see radio transmitter instructions).

o

Trigger telegram on the radio transmitter.
The status LED lights up for 5 seconds.
The actuator is connected to the radio transmitter. The actuator and radio transmitter exit
the programming mode automatically.

i

If the status LED of the control unit flashes 3 times at 1-second intervals for
approx. 5 seconds, then the programming operation was not successful. All the memory
locations in the actuator or radio transmitter are occupied. 

i

All On and All Off buttons of a radio transmitter are connected to the actuator automatically
as soon as the first connection to the radio transmitter takes place. Scene buttons must be
connected separately.

 Disconnecting connection to a radio transmitter

o

Carry out the same steps as when connecting (see Connecting to radio transmitter). 
The status LED (3) flashes quickly for 5 seconds. The actuator is disconnected from the
radio transmitter. The actuator and radio transmitter exit the programming mode
automatically.

i

If there several connections or scene buttons for a radio transmitter, all connections must
be disconnected individually.

i

All On and All Off buttons of a radio transmitter are disconnected automatically as soon as
the last connection to the radio transmitter is disconnected. Manual disconnection is not
possible. 

Resetting actuator to default setting

All connections to radio transmitters are disconnected and parameters are reset to default
setting.

i

The connections in the radio transmitters are preserved and must be deleted separately.

Load is switched off.

o

Press the 

Prog

 button for at least 20 seconds.

The status LED flashes after 4 seconds. After 20 seconds the status LED flashes faster.

o

Release 

Prog

 button and press briefly once again within 10 seconds.

The status LED flashes more slowly for approx. 5 seconds.

4/12

82581023
J0082581023

29.03.2017

eNet radio push-button controller 1-10 V 1-gang mini

Summary of Contents for FMST50UP

Page 1: ...t suitable for disconnection from supply voltage These instructions are an integral part of the product and must remain with the end customer 2 Device components Figure 1 Device components 1 Operating...

Page 2: ...eading of error memory Response after mains voltage return The response after mains voltage return can be configured with the eNet Server Default setting Off 4 Operation Operation with radio transmitt...

Page 3: ...to the device or load couple the miniature circuit breakers or label them with a warning to ensure disconnection is guaranteed o Insert the actuator in the appliance box in such a way that the Prog b...

Page 4: ...r are occupied i All On and All Off buttons of a radio transmitter are connected to the actuator automatically as soon as the first connection to the radio transmitter takes place Scene buttons must b...

Page 5: ...n be saved with a radio transmitter e g wall transmitter 6 Appendix 6 1 Technical data Rated voltage AC 230 V Mains frequency 50 60 Hz Standby power max 0 5 W Ambient temperature 25 70 C Contact type...

Page 6: ...are ignored Advanced device settings Parameters Setting options Basic setting Explanations Manual commissioning On Off Basic setting On Blocks manual commissioning for the device channel Note In the...

Page 7: ...ll remain off Note The set time apply to operation using radio transmitters The device is switched immediately when the Prog button is pressed Switch off delay 0 s 24 h Basic setting 0 s The load swit...

Page 8: ...run on time On Off Basic setting Off Allows manual switch off of a running run on time If the parameter is switched off then a switch off command will also switch the actuator on Only visible if a run...

Page 9: ...ightness value as scene value in an actuator for a command via a transmitter Switch off warning On Off Basic setting Off If the switch off warning is active then during switch off the systems dims to...

Page 10: ...r the channel Activate wind alarm brightness value 0 100 Basic setting 0 Defines the behaviour of the output on activating the wind alarm Deactivate wind alarm brightness value 0 100 Basic setting 0 D...

Page 11: ...h off on brightness overshoot Note This parameter is not yet active as a light controller has not yet been implemented Hotel function On Off Basic setting Off If the hotel function is activated the sy...

Page 12: ...rver for rail mounting Art No ENET SERVER 6 5 Conformity Albrecht Jung GmbH Co KG hereby declares that the radio system type Art No FMST50UP corresponds to the directive 2014 53 EU You can find the fu...

Reviews: