7 Commissioning
46
Basic setting
Temperature input
Administrator level/Password/Parameter level/Temperature input
Analog output
Administrator level/Password/Parameter level/Analog outputs/Analog output 1
Controller settings
See chapter 11.6.1 "Simple limit monitoring", page 78.
Start the basic settings, see chapter 6.7.3 "Basic setting", page 32
Diagrammatic overview, see chapter "Basic setting wizard", page 33.
Cell type
2-wire
Cell constant
0.01
Broken sensor detection
Off
Operating mode
Conductivity
Temperature compensation
None
Temperature compensation source
Temperature input
Unit
MOhm × cm
Display format
XX.xx
2nd measuring range
Off
Supply frequency
50 Hz
Reinitialize device
Yes
Temperature sensor
Pt100
Signal source
Main variable
Signal type
4 to 20 mA
Start of scaling
0.00 MOhm × cm
End of scaling
20.00 MOhm × cm