The choice of cable, the installation and the electrical connection must
conform to the requirements of VDE 0100 “Regulations on the Installation
of Power Circuits with Nominal Voltages below 1000 V” and the relevant
local regulations.
❏
At maximum load, the cable must be heat resistant up to at least 80 °C.
❏
The device is intended to be installed in electrical cabinets. It shall be
operated by mains protected with a branch circuitry overcurrent protection
device not more than 20 Amps.
For servicing/repairing a Disconnecting Device shall be provided to
disconnect all conductors.
❏
The load circuits must be fused for the maximum load currents in each case
to prevent the relay contacts from becoming welded in the event of a short
circuit.
❏
Electromagnetic compatibility meets the requirements of EN 61326.
❏
Lay the input, output, and supply lines so they are physically separated
from each other and are not parallel.
❏
Use twisted and shielded probe cables. If possible, do not lay these cables
close to components or cables through which current is flowing. Ground
the shielding at one end.
❏
The probe cables must have an uninterrupted run (do not route them via
terminal blocks or similar arrangements).
❏
No other consumers can be connected to the power terminals of the
instrument.
❏
The instrument is not suitable for installation in areas with an explosion
hazard.
❏
Apart from faulty installation, incorrect settings on the instrument may also
affect the proper functioning of the subsequent process or lead to damage.
You should therefore always provide safety equipment that is independent
of the instrument and it should only be possible for qualified personnel to
make settings.
Mounting information for conductor cross-sections and ferrules
The electrical connection must only be performed by
qualified personnel!
Ferrule
Conductor cross-section
Minimum length of ferrule or
stripping
Minimum Maximum
Without ferrule
0.34 mm
2
2.5 mm
2
10 mm (stripping)
Without collar
0.25 mm
2
2.5 mm
2
10 mm
With collar up to 1.5 mm
2
0.25 mm
2
1.5 mm
2
10 mm
Twin, with collar
0.25 mm
2
1.5 mm
2
12 mm