7
2 Compatibility and system requirements
2
Compatibility and system requirements
2.1
Certification
JUMO IO devices are certified by the PNO to Conformance Class B (abbreviated to CC-B) and net load
class "Netload Class III".
2.2
PROFINET IO and Ethernet standard services
The PROFINET interface supports all Ethernet standard services. Over this interface, the device can
also be accessed via the JUMO PC setup program and the JUMP PCC/PCA software. Additionally, the
JUMO field device can send its e-mails over this interface. The Ethernet standard services are also avail-
able during the cyclical PROFINET communication.
The PROFINET IO communication occurs in a parameterizable time pattern (RT channel). This ensures
that the IO data are transferred in real-time without being affected by Ethernet standard services. The
remaining time between the RT phases (NRT channel) is used for the communication between the
Ethernet standard services. Broadband bottlenecks impair the performance of the standard services.
The real-time capability of the PROFINET IO communication is guaranteed by the reserved RT channel.
2.3
Requirements for hardware, software, and cabling
Network installation
Any switches used to network PROFINET IO devices must support the following standards and func-
tions:
•
100 Mbit/s (transfer rate of the switchports)
•
Auto negotiation (automatic setting of the switchport transfer rate)
•
Cut through (direct relaying of the data between the switchports)
Full duplex support for the switchports
IEEE 802.1 Q (VLAN support for Priority Class 4 or higher)
The network installation must be executed compliant with the requirements of a 100Base TX Ethernet
network with cabling to CLASS D or higher.
JUMO AQUIS touch P
To use the PROFINET IO with JUMO AQUIS touch, the device must meet the following minimum re-
quirements:
•
Device software version 304.04.xx or higher
•
Hardware compatibility index 0x2 or higher
The information can be displayed and reviewed with the aid of the device menu.
Open device software version:
Device menu > Device info > General > Version > SW version
Open hardware compatibility index:
Device menu > Device info > General > Version > HW compatibility index
Summary of Contents for AQUIS touch P
Page 2: ......
Page 4: ...Contents...
Page 6: ...1 Safety information 6...
Page 8: ...2 Compatibility and system requirements 8...
Page 10: ...3 Electrical connection 10...
Page 46: ...6 Project planning 46...
Page 48: ...7 Error messages 48...
Page 49: ...49 8 Annex 8 Annex 8 1 PROFINET certificate...
Page 50: ...8 Annex 50...
Page 51: ......