5 Noncyclical data exchange
5.2
Data tables of noncyclical data
CAUTION!
All temperature values of the JUMO IO device are transferred in the unit "°C".
Misinterpretation of measured values of a JUMO IO device in the IO controller can cause errors in the
system control.
Respect the unit for the transferred temperature values!
5.2.1
Configuration data and parameters
Limit values for limit value monitoring 1 to 8
Limit values for temperature inputs IN4 and IN5
Limit values for universal inputs IN6, IN11 and IN12
Index
Signal designation
Data type
Access
2
84
0
3
0
Limit value monitoring 1 alarm 1
REAL
Read/Write
2
84
1
3
0
Limit value monitoring 1 alarm 2
REAL
Read/Write
2
84
2
3
0
Limit value monitoring 2 alarm 1
REAL
Read/Write
2
84
3
3
0
Limit value monitoring 2 alarm 2
REAL
Read/Write
2
84
4
3
0
Limit value monitoring 3 alarm 1
REAL
Read/Write
2
84
5
3
0
Limit value monitoring 3 alarm 2
REAL
Read/Write
2
84
6
3
0
Limit value monitoring 4 alarm 1
REAL
Read/Write
2
84
7
3
0
Limit value monitoring 4 alarm 2
REAL
Read/Write
2
84
8
3
0
Limit value monitoring 5 alarm 1
REAL
Read/Write
2
84
9
3
0
Limit value monitoring 5 alarm 2
REAL
Read/Write
2
84
10
3
0
Limit value monitoring 6 alarm 1
REAL
Read/Write
2
84
11
3
0
Limit value monitoring 6 alarm 2
REAL
Read/Write
2
84
12
3
0
Limit value monitoring 7 alarm 1
REAL
Read/Write
2
84
13
3
0
Limit value monitoring 7 alarm 2
REAL
Read/Write
2
84
14
3
0
Limit value monitoring 8 alarm 1
REAL
Read/Write
2
84
15
3
0
Limit value monitoring 8 alarm 2
REAL
Read/Write
Index
Signal designation
Data type
Access
2
44
0
3
0
Limit value for temperature input IN4 alarm 1
REAL
Read/Write
2
44
1
3
0
Limit value for temperature input IN4 alarm 2
REAL
Read/Write
2
44
2
3
0
Limit value for temperature input IN5 alarm 1
REAL
Read/Write
2
44
3
3
0
Limit value for temperature input IN4 alarm 2
REAL
Read/Write
Index
Signal designation
Data type
Access
2
48
0
3
0
Limit value for universal input IN6 alarm 1
REAL
Read/Write
2
48
1
3
0
Limit value for universal input IN6 alarm 2
REAL
Read/Write
2
48
2
3
0
Limit value for universal input IN11 alarm 1
REAL
Read/Write
2
48
3
3
0
Limit value for universal input IN11 alarm 2
REAL
Read/Write
2
48
4
3
0
Limit value for universal input IN12 alarm 1
REAL
Read/Write
2
48
5
3
0
Limit value for universal input IN12 alarm 2
REAL
Read/Write
Summary of Contents for AQUIS touch P
Page 2: ......
Page 4: ...Contents...
Page 6: ...1 Safety information 6...
Page 8: ...2 Compatibility and system requirements 8...
Page 10: ...3 Electrical connection 10...
Page 46: ...6 Project planning 46...
Page 48: ...7 Error messages 48...
Page 49: ...49 8 Annex 8 Annex 8 1 PROFINET certificate...
Page 50: ...8 Annex 50...
Page 51: ......