6 Project planning
40
6.3
Configuring the JUMO IO device
6.3.1
Start-up parameters
When the system boots, the start-up parameters are transferred from the IO controller to the JUMO field
device during the course of the IO device parameterization procedure. Prior to start-up, you must con-
figure the settings for the start-up parameters with the engineering system in the project planning of your
IO controller. The start-up parameters for each JUMO field device are located in the "DeviceStatusBlock"
module (Slot 1.)
The list of start-up parameters to be configured can be found in the module description.
chapter 4.2.2 "Modules", page 11
6.3.2
Communication parameters
Station name
To improve the overview in the IO controller project structure, each device should be assigned a self-
explanatory and preferably unique station name. This permits a better overview for programming and
project planning. The station name is entered in the engineering system of your IO controller at the PNIO
identification data of the JUMO IO device.
IP configuration
JUMO IO devices communicate with your PROFINET optional board via the internal Ethernet interface
of the device. In order for the PROFINET optional board in a JUMO IO device to become operational,
internal communication must be established between the optional board and the device. This requires
valid IP configuration of the Ethernet interface of the JUMO IO device. Without valid IP configuration of
the Ethernet interface, the device does not connect to the PROFINET IO interface and the PROFINET
optional board is not initialized.
Block diagram of a PROFINET optional board with its interfaces
(1) Ethernet slot in a JUMO IO device (COM2) with its own MAC address (cf. chapter 6.3.3 "Device in-
formation", page 43)
(2) Internal interface (SMK socket) of the PROFINET optional board for the slot in the JUMO IO device
with its own MAC address (PROFINET MAC address of the JUMO IO device, cf.
chapter 6.3.3 "Device information", page 43)
(3) PROFINET optional board
(4) Switchport RJ-45 with its own MAC address (cf. chapter 6.3.3 "Device information", page 43)
(5) Switchport RJ-45 with its own MAC address (cf. chapter 6.3.3 "Device information", page 43)
(1)
(2)
(3)
(4) (5)
Summary of Contents for AQUIS touch P
Page 2: ......
Page 4: ...Contents...
Page 6: ...1 Safety information 6...
Page 8: ...2 Compatibility and system requirements 8...
Page 10: ...3 Electrical connection 10...
Page 46: ...6 Project planning 46...
Page 48: ...7 Error messages 48...
Page 49: ...49 8 Annex 8 Annex 8 1 PROFINET certificate...
Page 50: ...8 Annex 50...
Page 51: ......